Function | Factory Default Options | Description |
Low Transfer | 120 V: | • 97 Vac | |
Point | 106 Vac | • 100 Vac | |
|
|
| • 103 Vac |
|
|
| • 106 Vac |
|
|
|
|
| 208 | V: | • 170 Vac |
| 182 | Vac | • 174 Vac |
|
|
| • 178 Vac |
|
|
| • 182 Vac |
|
|
|
|
| 230 | V: | • 196 Vac |
| 208 | Vac | • 200 Vac |
|
|
| • 204 Vac |
|
|
| • 208 Vac |
Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.This setting may also be adjusted using the power quality setting.
Note: Use the Advanced Menus to configure this setting.
Nominal Output 120 Vac | N/A | Set the nominal output voltage of the UPS on | |
Voltage |
|
| battery. This is available on 230 V models |
230 Vac | |||
|
|
| only. |
Transfer | High | High, Reduced, Low | Select the level of sensitivity to power events |
Sensitivity |
|
| that the UPS will tolerate. |
|
|
| • High: The UPS will go on battery power |
|
|
| more often to provide the cleanest power |
|
|
| supply to the connected equipment. |
|
|
| • Low: The UPS will tolerate more |
|
|
| fluctuations in power and will go on battery |
|
|
| power less often. |
|
|
| If the connected load is sensitive to power |
|
|
| disturbances, set the sensitivity to High. |
|
|
|
|
Low Battery | 120 sec | Set the value in | The UPS will emit an audible alarm when the |
Warning |
| seconds | remaining runtime has reached this level. |
|
|
| |
Date of Last | Date set at factory | Reset this date when the battery module is replaced. | |
Battery |
|
|
|
Replacement |
|
|
|
|
|
|
|
Audible Alarm | On | On/Off | The UPS will mute all audible alarms if this is |
|
|
| set to Off or when the display buttons are |
|
|
| pressed. |
|
|
|
|
Battery Self- | On | • Never | The interval at which the UPS will execute a |
Test Interval | every 14 days since • | ||
Setting | the last test | • Frequency of test |
|
|
| (days) |
|
|
|
| |
Reset to Factory No | Yes/No | Restore the UPS factory default settings. | |
Default |
|
|
|
8 |