Paradyne IPD4000E installation instructions DC Power Specifications

Page 9

DC Terminal Blocks

1.5.3 Establish a Power Connection

DC POWER SPECIFICATIONS

-48V DC

10 Amps maximum

Although actual power draw depends upon chassis configuration, a fully loaded chassis averages around 6 Amps.

1.5.3.1 Connect Your Positive Power Lead to the Terminal Block

Using a Phillips Screwdriver, remove the upper screw from the chosen terminal block (labeled "+" on the chassis). Slide the ring terminal of your positive power lead around the shaft of the screw and re-insert the screw into the same "+" terminal from which it was removed.

Ring

POSITIVE

Terminal

POWER LEAD

 

Positive (+)

Terminal

DC POWER

TERMINAL

1.5.3.2 Connect Your Negative Power Lead to the Terminal Block

Remove the right-hand screw (labeled "-") from the same terminal block. Slide the ring terminal of your NEGATIVE lead around the shaft of the screw and re-insert the screw into the same "-" terminal from which it was removed.

IPD4000E Installation Instructions 220-0000097 rev01

Page 9 of 17

Image 9
Contents IPD4000E Contents Operating Requirements Chassis SpecificationsRack Install Your Management Module Install Your Interface Modules Power Up Your IPD4000E Establish a Ground Connection DC Power Specifications Establish Your Uplink Connections Connect Your Subscriber Lines Detach the Velcro Strap Verify The Connections Document ContentsAdditional Information Customer Location Tech Support Email Tech Support Phone Regulatory ComplianceThis Class a product complies with European Norm EN55022