Compaq DA-11411 warranty Technical Specifications

Page 19

QuickSpecs

ProLiant BL20p and p-Class system

Technical Specifications

Compaq ProLiant BL p-Class

Dimensions

Height

10.5 in /26.67 cm

 

Server Blade Enclosure

 

Width

17.60 in/44.70 cm

 

 

 

 

 

 

Depth

28.86 in/73.30 cm

 

 

 

 

 

 

 

Input Specifications

Rated input voltage

-43 VDC to -53 VDC

Nominal -48 VDC

 

 

Rated input current

62.5 A at -48 VDC

 

 

 

Rated input Power

3000 W

 

 

 

 

 

 

 

Individual server blade bay

Rated input voltage

-43 VDC to -53 VDC

Nominal -48 VDC

 

ratings

Rated input current

6.25 A at -48 VDC

 

 

 

 

 

 

Rated input Power

300 W

 

 

 

 

 

 

Temperature range

Operating

50° to 95° F/10° to 35° C

 

 

Non-Operating

-22° to 140° F/-30° to 60° C

 

 

 

 

 

 

Relative humidity

Operating

20% to 80%

 

 

(non-condensing)

Non-Operating

5% to 95%

 

 

 

 

 

 

 

 

 

 

Wet bulb temperature

Operating

82.4° F/28° C

 

 

 

Non-Operating

101.7° F/38.7° C

 

Note: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft/ 9,144 m or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of 113° F/45° C. Altitude maximum for storage is 70 KPa.

Operating and Performance Specifications for ProLiant BL20p Server Blade

Dimensions

Height

1.69 in/4.29 cm

 

Width

10.29 in/26.14 cm

 

Depth

28.00 in/71.12 cm

 

 

 

Weight (maximum)

18.0 lb/8.17 kg

 

 

 

 

Temperature range

Operating

50° to 95° F/10° to 35° C

 

Non-operating

 

 

Shipping

-40° to 140° F/-40° to 60° C

 

Storage

-4° to 140° F/-20° to 60° C

 

 

 

Relative humidity

Operating

10% to 90%

(non-condensing)

Non-operating

 

 

 

 

Shipping

10% to 90%

 

Storage

10% to 95%

 

 

 

Maximum wet bulb

82° F/28° C

 

temperature

 

 

Note: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft/ 9,144 m or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of 113° F/45° C. Altitude maximum for storage is 70 KPa.

DA-11411

World Wide — Version 4 — September 19, 2002

19

Image 19 Contents
Overview QuickSpecsConfiguration Steps Standard Features Server Blade ProLiant BL p Class RJ 45 patch panel ProLiant BL p Class Interconnect Switch OptionRequired Network Cabling Power Bus Box Required Power Source Compaq ProLiant BL p Class Power System and RackInformation ProLiant BL p Class Power BL p Class Power DistributionProLiant Essentials Foundation Pack Software Standard FeaturesIntelligent Manageability OS SupportAvailability Minimum Rack Requirements SecurityRack Airflow Requirements Service and Support Models Options Storage Controllers ProLiant Essentials Value Pack SoftwareCommunications BL p-Class Server Blade BL p-Class Power optionsPower Distribution Diagnostic OptionsCompaq Rack 9000 Series Opal Compaq Rack 10000 Series Rack Options for Compaq Rack 7000 Series and Telco racks Rack Options for Compaq Rack Series Rack Options for Compaq Rack 9000 SeriesRack Options for Compaq Rack 10000, 9000 and 7000 Series Service and Support OfferingsRack Options for Telco Racks Installation & Start-up Services Memory Slot MemoryTechnical Specifications Power requirements Operating and Performance DimensionsSpecifications for RJ-45 Patch Panel ConnectorPerformance WeightForwarding mode SafetyInput requirements WeightsSpecifications Ambient temperatureQuickSpecs Rated operating voltage Enclosures DimensionsMax total power supported Max current per power feedCurrent Specifications for Facility DCMax Rated Power Operating and Performance VoltageCompaq Rack Dimensions Total Cabinet Shipping Color QuickSpecs