European Union Directives

A–5

AC Mains Filters DL05, DL205 and DL305 AC powered base power supplies require extra mains filtering to comply with the EMC Directive on conducted RF emissions. All PLC equipment has been

Schaffner

tested with filters from Schaffner, which reduce emissions levels if the filters are properly grounded (earth ground). A filter with a current rating suitable to supply all PLC power supplies and AC input modules should be selected. We suggest the

Filter

FN2010

To AC

Input

Transient Circuitry

Suppressor

Fused

FN2010 for DL05/DL205 systems and the FN2080 for DL305 systems. DL405 systems do not require extra filtering.

EarthTerminals

Terminal

L N

NOTE: Very few mains filters can reduce problem emissions to negligible levels. In some cases, filters may increase conducted emissions if not properly matched to the problem emissions.

Suppression and In order to comply with the fire risk requirements of the Low Voltage and Machinery

FusingDirective electrical standards EN 61010–1, and EN 60204–1, by limiting the power into “unlimited” mains circuits with power leads reversed, it is necessary to fuse both AC and DC supply inputs. You should also install a transient voltage suppressor across the power input connections of the PLC. Choose a suppressor such as a metal oxide varistor, with a rating of 275VAC working voltage for 230V nominal supplies (150VAC working voltage for 115V supplies) and high energy capacity (eg. 140 joules).

Transient suppressors must be protected by fuses and the capacity of the transient suppressor must be greater than the blow characteristics of the fuses or circuit breakers to avoid a fire risk. A recommended AC supply input arrangement for Koyo PLCs is to use twin 3 amp TT fused terminals with fuse blown indication, such as DINnectors DN–F10L terminals, or twin circuit breakers, wired to a Schaffner FN2010 filter or equivalent, with high energy transient suppressor soldered directly across the output terminals of the filter. PLC system inputs should also be protected from voltage impulses by deriving their power from the same fused, filtered, and surge-suppressed supply.

Internal Enclosure A heavy-duty star earth terminal block should be provided in every cubicle for the

Groundingconnection of all earth ground straps, protective earth ground connections, mains filter earth ground wires, and mechanical assembly earth ground connections. This should be installed to comply with safety and EMC requirements, local standards, and the requirements found in IEC 1000–5–2.The Machinery Directive also requires that the common terminals of PLC input modules, and common supply side of loads driven from PLC output modules should be connected to the protective earth ground terminal.

Image 31
Contents D4-470 Trademarks Table of Contents Appendix a European Union Directives CE Iii Manual RevisionsThis Chapter Introduction to the D4-470Manual Overview Provides CE information Special SymbolsChapters AppendicesPentium D4-470 OverviewProcessor Configuration Choices Accessories Installation, Wiring, and Specifications Mounting and Wiring Guidelines Agency EnclosuresApprovals Power Wiring Left Side Ports and ConnectorsRight Side General Specifications of the D4-470 Technical and Environmental SpecificationsFunctional Specifications Functional Specifications cont’d Dimensions Installing Hardware Accessories Adding Third-Party Boards to Expansion Slots Panels Knock-outDual In-line Memory Module Installing Additional RAM MemoryInstalling MemoryChanging the CPU Powering Internal and External DevicesThis Appendix European Union Directives CEMember Countries Applicable Directives Compliance European Union EU DirectivesProduct Specific Standard for PLCs EMC Directive Standards Revelant to PLCsBritish Standards Institution Sales Department Basic EMC Installation GuidelinesSchaffner Communications Shielded Cables Equi-potential GroundingShielded Cables within Enclosures Network Isolation Items Specific to the D4-470 Maintenance of the D4-470