LG Electronics D4470 user manual Equi-potential Grounding, Communications Shielded Cables

Page 32

A–6

European Union Directives

Equi–potential

Grounding

Key

 

Serial Communication Cable

 

 

Equi-potential Bond

 

 

Adequate site earth grounding must be provided for equipment containing modern electronic circuitry. The use of isolated earth electrodes for electronic systems is forbidden in some countries. Make sure you check any requirements for your particular destination. IEC 1000–5–2 covers equi-potential bonding of earth grids adequately, but special attention should be given to apparatus and control cubicles that contain I/O devices, remote I/O racks, or have inter-system communications with the primary PLC system enclosure. An equi-potential bond wire must be provided alongside all serial communications cables, and to any separate items of the plant which contain I/O devices connected to the PLC. The diagram shows an example of four physical locations connected by a communications cable.

Communications

and Shielded

Cables

Screened

Cable

Equi-potential

Bond

Conductive

Adapter

Serial

I/O

To Earth

Block

Control Cubicle

Good quality 24 AWG minimum twisted-pair shielded cables, with overall foil and braid shields are recommended for analog cabling and communications cabling outside of the PLC enclosure. To date it has been a common practice to only provide an earth ground for one end of the cable shield in order to minimize the risk of noise caused by earth ground loop currents between apparatus. The procedure of only grounding one end, which primarily originated as a result of trying to reduce hum in audio systems, is no longer applicable to the complex industrial environment. Shielded cables are also efficient emitters of RF noise from the PLC system, and can interact in a parasitic manner in networks and between multiple sources of interference.

Image 32
Contents D4-470 Trademarks Table of Contents Appendix a European Union Directives CE Manual Revisions IiiIntroduction to the D4-470 This ChapterManual Overview Special Symbols ChaptersAppendices Provides CE informationProcessor D4-470 OverviewPentium Configuration Choices Accessories Installation, Wiring, and Specifications Mounting and Wiring Guidelines Approvals EnclosuresAgency Power Wiring Ports and Connectors Left SideRight Side Technical and Environmental Specifications General Specifications of the D4-470Functional Specifications Functional Specifications cont’d Dimensions Installing Hardware Accessories Adding Third-Party Boards to Expansion Slots Knock-out PanelsInstalling Additional RAM Memory InstallingMemory Dual In-line Memory ModulePowering Internal and External Devices Changing the CPUEuropean Union Directives CE This AppendixEuropean Union EU Directives Member Countries Applicable Directives ComplianceEMC Directive Standards Revelant to PLCs Product Specific Standard for PLCsBasic EMC Installation Guidelines British Standards Institution Sales DepartmentSchaffner Equi-potential Grounding Communications Shielded CablesShielded Cables within Enclosures Network Isolation Items Specific to the D4-470 Maintenance of the D4-470