2.At the “Ethernet Operation Setting window”, one can configure the IP address of the Ethernet module.
a.Set the Communication Data Code to Binary
b.Check the “Enable Online Change” checkbox
c.Select the “Initial Timing” to be Always wait for OPEN (Communication possible at STOP time). This is a critical step to ensure proper communication between the Ethernet module and the ICC
d.Select the “Use the KeepAlive” function.
e.Click “End” to return to the Network Parameter Setting Window