Texas Instruments SLVP089 manual Controller Functions

Page 24
Design Procedures

2.3.6Controller Functions

The controller functions, oscillator frequency, soft-start, dead-time-control, short-circuit protection, and sense-divider-network are discussed in this sec- tion.

The oscillator frequency is set by selecting the resistance value from the graph in figure 6 of the TL5001 data sheet. For 100 kHz, a value of 90.9 kWis se- lected.

Dead-time control provides a minimum off-time for the power switch in each cycle. Set this time by connecting a resistor between DTC and GND. For this

design, a maximum duty cycle of 100% is chosen. Then R8 is calculated as:

R8

(R9 )1.25)

103

￿D￿V

O(100%)

– V

O(0%)

￿)V

O(0%)

￿

 

 

 

 

 

 

 

 

+(90.9 )1.25)

103

[1(1.3 – 0.65) )0.65]

 

 

119.8 K121 kW

Soft-start is added to reduce power-up transients. This is implemented by ad- ding a capacitor across the dead-time resistor. In this design, a soft-start time of 25 ms is used:

C +

tR

 

+0.025 s

+0.21 mF

RDT

121 kW

 

 

The TL5001 has short circuit protection instead of a current sense circuit. If not used, the SCP terminal must be connected to ground to allow the converter to start up. If a timing capacitor is connected to SCP, it should have a time constant that is greater than the soft-start time constant. This time constant is chosen to be 75 ms:

C(mF) +12.46 tSCP +12.46 0.075 s +0.93 mF

2.3.7Loop Compensation

Loop compensation is necessary to stabilize the converter over the full range of load, line, and gain conditions. A buck-mode converter has a two-pole LC output filter with a 40-dB-per-decade rolloff. The total closed-loop response needed for stability is a 20-dB-per-decade rolloff with a minimum phase margin of 30 degrees over the full bandwidth for all conditions. In addition, sufficient bandwidth must be designed into the circuit to assure that the converter will have good transient response. Both of these requirements are achieved by ad- ding compensation components around the error amplifier to modify the total loop response.

The first step in design of the loop compensation network is the design of the output sense divider. This sets the output voltage and the top resistor deter- mines the relative size of the rest of the compensation design. Since the TL5001 input bias current is 0.5 mA (worst case), the divider current should be at least 0.5 mA. Using a 1-kWresistor for the bottom of the divider gives a divid- er current of 1 mA. The top of the divider is calculated as:

R +

￿VO 1￿

+(3.3 –1)

+2.3 kW

1 mA

 

0.001

2-6

Image 24
Contents User’s Guide 07/98 Literature Number SLVU001A July Important Notice Read This First About This ManualTrademarks Contents Figures TablesHardware TopicIntroduction Typical Synchronous Buck ConverterSchematic Schematic DiagramPower Supply Input/Output ConnectionsBoard Layout Shows the SLVP089 board layoutBill of Materials Bill of MaterialsTest Results Load Regulation and Ripple, 3.3-V 9-V InputPower Switch Turn-On and Delay from Q2 Off Inductor and Output Ripple Page Design Procedure Introduction Operating Specifications Operating SpecificationsDesign Procedures Duty Cycle Estimate+ 3 W Controller Functions + DD V O Compensation Network Bode Plot