6 |
8.Apply power to the PSU
For AC Models:
Read the
Plug the provided AC power cord into the AC power inlet on the rear panel of the PSU and connect the PSU to the mains power supply.
Important information for service personnel only:
•CAUTION: double pole/neutral fusing
•The ratings of fuses FH101 and FH102 is 250 V, 5 A
For DC models:
Read the
Only trained and qualified personnel should connect a DC power supply.
For centralized DC power connection, the switch should be installed only in Restricted Access Areas (Dedicated Equipment Rooms, Equipment Closets, or the like) in accordance with Articles
DC supply cable specifications:
•Three core cable is required
•Minimum core size: 3.3 mm2 (12 AWG) high strand count copper wire
•Minimum cable rating: 600 V, 90 degrees Celsius
DC power supply specifications:
•40 to 60 V, 48 V nominal
•Supports either positive grounded or negative grounded operation Circuit protection:
•10 Amp certified/Listed circuit breaker is required for branch circuit protection
To connect the DC supply:
Ensure that the supply cable is not live.
1.Remove the transparent protective terminal cover.
2.Strip the supply cable wires to expose 7.5mm (0.31 in.) of bare conductor. Terminate with JST
3.Connect the ground wire to the ground terminal. Terminals can be identified by the diagram on the switch’s rear panel. Tighten the terminal to between 2.4 and 4.0 Nm (21.3 and 35.4 lbf in).