Powerware 415/240V, 400/230V, 380/220V, 208/120V Configuring Panels Containing Subfeed Breakers

Page 50

OPERATION

4.On the PANEL CONFIG screen, set the panel’s meter settings:

Default

Range

Meter Setting

Description

 

 

 

 

3

3

PHASES

Number of phases

 

 

 

 

42

0–42

BREAKERS

Number of branch circuit

 

(even numbers)

 

breakers in the panel

 

 

 

 

100

0–1200

RATING

Panel breaker rating (in amps)

 

 

 

(see Note 1)

 

 

 

 

STANDARD

STANDARD

PNL LAYOUT

Panel layout

 

COLUMN

 

(see Note 2)

 

 

 

 

NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker alarms and zeroes the panel percent current levels.

NOTE 2 Changing panel layout erases all branch circuit breaker configurations.

To reset all values on the screen to defaults, set the RESET value to

YES.

5.Select OK.

6.Repeat Steps 3 to 5 for each panel containing branch circuit breakers to configure.

7.When all panel configuration is complete, select the button repeatedly to reach the main menu.

8.If all configuration is complete, save your changes by pressing the Reset button on the Power Xpert Gateway Card in the X−Slot communication bay. (The card automatically resets after five minutes.) Otherwise, continue to

Breakers" on page 46.

Configuring Panels Containing Subfeed Breakers

To configure panels containing subfeed breakers (up to 12 per panel):

1.If not already obtained, access the System Setup Level 1 password level. See

2.From the main menu, select METER then PANEL.

3.On the PANEL screen, select the panel number (PNL) to configure, and then select CONFIG.

44 EATON Powerware® Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com

Image 50
Contents Page Requesting a Declaration of Conformity Special Symbols Three−phase alternating currentPage Table of Contents Specifications Troubleshooting Serial Port Service −Slot CardMaintenance WarrantyChapter Introduction Introduction Important Safety Instructions Safety WarningsConsignes de sécurité N G E RWichtige Sicherheitsanweisungen Aufbewaren SicherheitswarnungenAdvertencias de Seguridad L I G R OInspecting the Equipment Unpacking the CabinetChecking the Parts List Tools Required Installing the Hardware Wall Specifications Customer−Supplied ComponentsMounting Template Conduit Box Option Electrical Connections R N I N GWire Tap Sizing Current Transformer SizingWiring Overview Example Installation Harness SizingCT1 Panel Detail EMS−UGK−LV Model with Dual Panel Option Shown Main Input Harness Connections Branch Circuit Harness Connections Install each CT around the appropriate subfeed breaker wire Subfeed Monitoring ConnectionsU T I O N Proceed to on Installation Power LED on the Power Xpert Gateway Series 1000 Card Microsoft Windows XP or Windows 2000 operating system Initial ConfigurationInstalling the Software Configuration Tool Initial System Configuration Click Connect to establish communication with the EMS−UGKSystem Status Page Connected Type the new name. Press Enter, then click Yes to confirm Installation Configure the following Building Alarm Settings Feature Setting Description Audible Horn DisabledInstallation Configure the following settings for the selected panel Installation Initial Panel and Breaker Configuration Using the Display Installation Advanced Metering Installation Power Xpert Gateway Series 1000 CardBoard UCB Reset FunctionBreaker Numbering Following table shows the indicator status and description Control Panel FunctionsDisplay Functions Buttons to select another item on the screen toMenu Map for Display Functions Menu MapFollowing tables show the basic menu structure Panel Meters Breaker MetersSetup Options Building AlarmConfiguring Panels Containing Branch Circuit Breakers Control Panel ConfigurationAccessing Configuration Configuring Panels Containing Subfeed Breakers On the Panel Config screen, set the panel’s meter settingsNumber of subfeed breakers Configuring Branch Circuit Breakers OverloadDelete Viewing Panel Meters Viewing Breaker MetersCommunication Communication Options Installing Communication FeaturesSerial Port Service Terminal Mode −Slot CardControl Terminals External Control Terminal ConnectionsRelay Output Contacts Alarm Relay Programmable Signal Inputs Building AlarmsCommunication Chapter Maintenance Recycling the Used EquipmentRewiring and Reconfiguring the Installation To rewire and reconfigure the EMS−UGKDimensions and Weight Communication OptionsDisplay Optional Environmental and SafetyElectrical Input Metering Panel Monitoring Rating Maximum 400ASpecifications Typical Alarms and Conditions Service and SupportTroubleshooting Limited Factory Warranty Powerware Energy Management System EMS Upgrade KitWarranty Page 164201724

415/240V, 380/220V, 208/120V, 400/230V specifications

The Powerware series of uninterruptible power supplies (UPS) is renowned for its versatility and reliability in providing essential power protection for critical equipment across various environments. Specifically, the configurations of 208/120V, 400/230V, 380/220V, and 415/240V cater to a wide range of geographic voltage standards, making it an ideal solution for diverse industrial and commercial applications.

One of the defining features of the Powerware UPS is its robust architecture which ensures high availability and reliability. Designed for mission-critical environments, these units often come equipped with advanced technologies that facilitate seamless operation during power interruptions or fluctuations.

The Powerware UPS employs double-conversion online technology that offers superior protection by continuously converting incoming AC power to DC and then back to AC. This process isolates the connected equipment from all power disturbances, such as surges, sags, and electrical noise, thus ensuring clean and stable output power. With this technology, users can rest assured that their sensitive electronics and IT infrastructure are shielded from any potential damage caused by irregular power supply.

Additionally, the Powerware series includes intelligent battery management systems that extend battery life and optimize performance. This feature involves real-time monitoring of battery health and automatic adjustment of charging methods to enhance efficiency. Users benefit from reduced maintenance costs and increased operational uptime due to improved battery management.

Moreover, the Powerware UPS is designed with scalability in mind. These units can be configured in parallel for load sharing, allowing organizations to expand their power capacity as needed without having to invest in entirely new systems. This flexibility is particularly beneficial for growing businesses that anticipate increased power needs over time.

The compact design and enhanced cooling systems further characterize the Powerware UPS, making it suitable for installations in space-constrained environments. The units are often equipped with user-friendly interfaces, providing easy access to critical information and diagnostics for power management.

In summary, the Powerware series with 208/120V, 400/230V, 380/220V, and 415/240V configurations represents a comprehensive solution for ensuring uninterrupted power supply in various settings. Its advanced technology, battery management features, scalability, and space-saving design make it an excellent choice for organizations seeking reliable power protection.