3. Physical Layout of the Sima STP-3000
Power flows logically from the rear terminals of the Sima
NOTE: It is extremely important to provide adequate airspace around the unit surfaces to allow for convection cooling as described in Section 5.1 – Where To Install.
Figure 3. AC and DC panels of the SIMA STP-3000
A. AC PANEL
OVERLOAD INDICATOR:
Lights when inverter shuts down because of severe overload. Turn inverter off. Remove cause of overload, and turn inverter on to reset .
ON/OFF SWITCH:
Leave in OFF position during installation
CAUTION! THIS IS NOT A DISCONNECT SWITCH.
REMOVE POWER AT THE SOURCE BEFORE SERVICING.
OVER TEMP INDICATOR: Inverter is shut down while indicator is ON. Inverter will restart automatically.
Indicator lamp and alarm will turn off when the inverter cools. Lights and alarm alerts when inverter protects itself against OVERHEATING.
BAR GRAPH METERS:
Display battery voltage and current. Current should be in the GREEN zone ONLY for continuous operation; The inverter will operate for several minutes when the current in the Yellow zone: operation with battery voltage or current in the red zone of the meter will result in protective shutdown of the inverter.
|
|
|
| |
|
|
|
| |
Modular jack |
|
| ||
AC GFI outlet (Inverter output) | ||||
for Remote control |
| |||
|
| |||
|
|
|
| |
|
|
|
|
B. DC PANEL
Ventilation Opening
DO NOT OBSTRUCT – Allow at least 4 inch (100 mm) clearance for air flow.
RED: Positive “+”
CAUTION: Reverse polarity will open internal fuses and MAY damage the inverter permanently
BLACK: Negative
CHASSIS GROUND LUG.
WARNING: Operation of the inverter without a proper ground connection may result in an electrical safety hazard
Page 4 of 14