Western Telematic 12651 manual Page8, Power-Up Default String

Page 10

RPB+User'sGuide

4.1. The Power-Up Default String

The Power-Up Default String allows the user to select default On/Off conditions for each switched AC outlet. When the RPB+ is powered up, or when the /D command (Set Defaults) is invoked, each outlet will be set according to the Default String.

Note:

￿The Power-Up Default String includes five characters; each character determines the default On/Off condition for the corresponding plug. The first character applies to Plug 1, the second character applies to Plug 2, and etc..

￿To set a plug to default "ON" enter a one (1); to set a plug to default "OFF", enter a zero (0).

￿If the Default String includes invalid or missing characters, plugs will be switched “Off” when the unit is powered up, regardless of the conditions shown by the Status Screen. In addition, the /D command will not function.

Example 1: To set default On/Off conditions as follows:

ON: Plugs 1 and 5

OFF: Plugs 2, 3, and 4

The Power-Up Default String would be defined as "10001".

Example 2: To set default plug conditions as follows:

ON: Plugs 3, 4, and 5

OFF: Plugs 1 and 2

The Power-Up Default String would be defined as "00111".

Page8

Image 10
Contents WTIPartNo.Rev12651.B Page Introduction FeaturesBold Font Unit Description Front PanelUnitDescription Back PanelRead Only Mode When e InstallationSetUp Switches Control Port Connection Installation Power ConnectionStart-Up / Configuration Page Power-Up Default String Page8Operation OperationOn / OFF / Boot Examples Page10Power Appendix a SpecificationsRS232 Port Customer Service