DESCRIPTION & SPECIFICATIONS
DESCRIPTION:
The OMEGA DPF70 is a dual input (channel A and B) counter/ ratemeter, each with its own 5 digit dividing scale factor. The two 5 AMP preset relay outputs can be programmed by the user to apply to the "A" total counter, the "A" ratemeter, or the "B" counter or the net total of A and B inputs. The user can view the Net Total of "A+B", the Net Total of
SPECIFICATIONS:
DISPLAY
6 digit, 0.55" High LED
INPUT POWER:
110 VAC ± 15% or 11 to 15 VDC
220 VAC ± 15% or 11 to 15 VDC
CURRENT:
250 mA DC max. or 6.5 VA AC
OUTPUT POWER (AC powered units only) +12 VDC @ 50 mA, unregulated
TEMPERATURE:
Operating: +32°F (0°C) to +130 F (+54°C)
Storage:
DIMENSIONS: See next page.
WEIGHT:
2 Lbs. (1 kg)
MEMORY
EEPROM stores data for 10 years if power is lost.
INPUTS:
3:High Impedance DC pulse input Open or
(low),
3M: Mag. Input, Input A only, accepts 30mV input (50 V max. P/P) signals 10 KOhm imp. 5 KHz max. (Input B,
3MB: Mag. Input, Inputs A & B, accepts 30mV input (50 V max. P/P) signals 10 KOhm imp. 5 KHz max.
5:
Control input (level) on Input B.
5M: 30 mV Count pulses on Input A (50 V max. P/P)
9:Quadrature, accepts
9MB: Quadrature, accepts 30 mV (50 V max. P/P) pulses with 90°phase shift for direction detection.
NOTE: The Mag. inputs have filtering as follows: up to 300hz @30mV, 5KHz @ .25V to 50V max.
RESET: Front Panel:
Resets displayed value and control output Remote:
K FACTOR/SCALING
In the standard unit a fixed
CONTROL OUTPUTS:
Relays:
2 each N.O. Relay; 5 Amps120/240 VAC or 28 VDC. (N.C. relay contacts and NPN transistor output available with solder jumpers. Transistor output is internally pulled up to 10 VDC through relay coil, sinks from 10 VDC to .5 V @ 100 mA)
Analog Output:
An optional
Accuracy: 50uA worst case.
Compliance Voltage: 3 to 30 VDC non inductive.
RS232/RS422SERIAL INTERFACE
If the serial interface option is supplied, up to 99 units can be linked together. (The terminal addressing the unit must be capable of driving all loads in the loop.) Unit status and new set points can be communicated by serial communication. Mode changes, however, must always be made on the front panel. Data is transmitted at selected baud rates using standard seven bit ASCII characters and parity with two additional bits of “Start” and “Stop” to make up the standard ten bit character.
Data is received and transmitted over standard EIA RS232 or RS422 levels. Each 10 bit character is made up of a start bit, 7 bit ASCII code, parity bit and stop bit. Unit number, baud rate and parity are entered in the “Program Setting” set up mode and remain in memory even if power is off.
Note that the input impedance of RS232 is 3K or 7K Ohm worst case. The terminal addressing the unit must be capable of driving all loads in the loop. RS422 input impedance is much higher and there is usually no problem driving 25 units. Unit serial transmit line remains in a high impedance “OFF” state until addressed.
PRESETS
Two control outputs are provided. To set relay values, press “menu” button until “Relay” appears on the display, the A and B outputs can be assigned to the ratemeter (high/low), one preset for rate and one for total, or two presets (2 stage shut off) on the A and B counters. A 5 digit value can be entered for both presets and the decimal point location is the same as the counter. The outputs can be set to energize from 0.1 to 99.9 seconds or latch (0.0). If a value other than 0.0 is entered, the counters will auto reset at the preset . In the
LOCKOUT
Unauthorized front panel changes can be prevented by entering a user selected 5 digit code, in the “LOC” , . mode. The front panel can be completely locked out or the presets can remain accessible.
RATEMETER
Accurate to 4 1/2 digits (±1 display digit). The rate meter can be programmed to accept almost any number of pulses per unit of measurement, sample from 2 to 24 seconds maximum, and auto- range up to 5 digits of significant information. In the “RPS” mode, the ratemeter displays in units per second, and in the “scale” mode, units per hour or per minute. The unit will display the rate of the A Input only.
COUNTER
The two
1