Omega Vehicle Security CN3271 Series manual Hi.Lo = High and low limit for special process

Page 14

Hi. = High limit (for heating process) Lo. = Low limit (for cooling process)

Hi.Lo = High and low limit (for special process)

C2 = Rearming Mode

O = Acknowledgements rearm (reset) the limiter (and restart the process) only if the condition which generated the shutdown status no longer exists (points A and C of the Example 1). It do not generate any effect if the condition which generated the shutdown status still exists (point B of the Example 1).

I = Acknowledgements enable the automatic rearmament (reset) of the limiter if the condition which generated the shutdown status still exists (point B of the Example 2). (The instrument rearms (reset) automatically when the condition which generated the shutdown status no longer exists).

Notes about limiter function

The relay of the output 1 operates in fail-safe mode (relay de-energized during shutdown condition) and latching mode.

The OUT 1 turns OFF when:

-C1 = Hi and the measured value is greater than limiter threshold [“Su” parameter (see Operative parameters”)] or

-C1 = LO and the measured value is less than limiter threshold [“Su” parameter (see Operative parameters”)] or

-C1 = HiLO and the measured value is greater than “Su” parameter (see Operative parameters”)

or less than “S1” parameter (see Operative parameters”).

The Out 1 remains OFF until the condition which

generated the shutdown, no longer exists and the acknowledge action has been performed.

The upper display flashes during a shutdown and returns to a steady display when the shutdown condition no longer exists.

When C2 = 0 and OUT 1 is OFF, the RESET LED is ON.

When C2 = 1 one of the following condition may occur:

-if no acknowledgement has been made, OUT 1 is OFF and the RESET LED is flashing;

-if the acknowledgement has been made but the condition which generated the shutdown status still exists, OUT 1 is OFF and the RESET LED is steady ON.

The shutdown condition can be stored in permanent memory (see C4).

Acknowledgment can be performed by pressing the RESET key, by momentarily closing the external dry contact or by a command from the serial link.

The length of the shutdown condition and max/min measured values are stored in memory and available for viewing until the next shutdown condition occurs.

These informations are lost at power down. During a shutdown condition the max/min measured values are continuously updated and can be monitored.

Example 1 - C1 = Hi and C2 = O

11

LHL-1-NEUTRO.pmd

11

19/04/2004, 15.07

Image 14
Contents CN3271-add2.pmd 19/08/2004 OMEGAnet On-LineService Internet e-mail Info@omega.com Contents Screw Bracket Panel Mounting RequirementsDimensions and Rear Terminal Blocks Without RS-485 With RS-485Panel Cutout Wiring Guidelines MA, mV and V Inputs Wiring RTD Input Linear InputOUT 1 Class Logic Input for models with RS-485 onlyRelay Outputs Use cupper conductors onlyInductive Loads Serial Interface100 to 240 Vac Power Line and groundingAA/A 500 mA 250 100/240 V AC 125 mAHigh Low Limiter with RS-485 High Low Limiter without RS-485Serial Interface Protocol Configuration KEY FunctionsConfiguration Procedure Type R5 = Offset AdjustmentR7 = Alarm action on input fault Value R2 = Decimal Point PositionC2 = Rearming Mode Hi.Lo = High and low limit for special process= Alarm configuration = Rearm at Power-up Auto = Automatic rearmConstant Alarm Function = Shutdown memoryExample for P2 = H.L P3 = Alarm ActionExample for P2 = H.A.A.c T1 = Timeout Selection Alarm Standby mask Function= Safety Lock Operating Mode Normal Display ModeNormal Display Mode to Operative Parameter Display Mode IndicatorsFlashes when alarm is on Operative Parameter Display ModeOperating Parameters Limiter function Example 1 C1 = Hi and C2 = O Example 2 C1 = Hi and C2 =Device can be connected to a host computer via serial link Alarm functionsSerial LInk optional Error List Error MessagesError Messages Dealing with Error MessagesCommon mode rejection ratio General SpecificationsPower consumption 8 VA Temperature Drift CJ excludedInputs Thermocouple Linear InputsOutputs AlarmLogic Inputs OutputMaintenance Serial Communication Interface OptionDefault Parameters Default Operating Parameters ListLHL-A-NEUTRO.pmd 19/04/2004 Second Seconds Appendix A.3 Appendix B Thermocouple Compensating Cable Color Codes Return Requests / Inquiries Data Acquisition