Omega Vehicle Security CN3271 Series manual Inputs Thermocouple, Linear Inputs

Page 25

INPUTS

A) THERMOCOUPLE

Type : J, K, T, E, N, S, R, B, L, U, G(W), D(W3), C(W5), Platinel II, °C/°F selectable.

External resistance: 100 max, maximum error 0,1% of span.

Burn out: It is shown as an overrange condition (standard). It is possible to obtain an underrange indication by cut and short.

Cold junction: automatic compensation from 0 to 50 °C.

Cold junction accuracy : 0.1 °C/°C

Input impedance: > 1 M

Calibration : according to IEC 584-1 and DIN 43710 - 1977.

STANDARD RANGES TABLE

T/C

 

 

 

 

Ranges

 

 

 

type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

0

 

-100 / 1000 °C

23

 

-150 / 1830

°F

K

1

 

-100 / 1370 °C

24

 

-150 / 2500

°F

T

2

 

-200 /

400

°C

25

 

-330 / 750

°F

E

3

 

-100 /

800

°C

26

 

-150 / 1470

°F

N

4

 

-100 / 1400 °C

27

 

-150 / 2550

°F

S

5

 

-50 / 1760 °C

28

 

-60 / 3200

°F

R

6

 

-50 / 1760 °C

29

 

-60 / 3200

°F

B

7

 

0 / 1820 °C

30

 

32

/ 3300

°F

L

8

 

-100 /

900

°C

31

 

-150 / 1650

°F

U

9

 

-200 /

600

°C

32

 

-330 / 1110

°F

G(W)

10

 

0 / 2300 °C

33

 

0

/ 4170

°F

D(W3)

11

 

0 / 2300 °C

34

 

0

/ 4170

°F

C(W5)

12

 

0 / 2300 °C

35

 

0

/ 4170

°F

P.(*)

13

 

-100 / 1400 °C

36

 

-150 / 2550

°F

 

 

 

 

 

 

 

 

 

 

(*) P. equal

to Platinel II

 

 

 

 

 

 

B)RTD (Resistance Temperature Detector) Input: for RTD Pt 100 , 3 wire connection. Input circuit: current injection.

°C/°F selection: via front pushbuttons or serial link.

Line resistance: automatic compensation up to 20 /wire with no measurable error.

Calibration: according to DIN 43760

Burn out : The instrument detect the open condition of one or more wires. It is able to detect also the short circuit of the sensor.

STANDARD RANGES TABLE

Input

 

Ranges

 

type

 

 

 

 

 

 

 

 

 

 

 

RTD Pt 100

14

- 200

/ 850

°C

DIN 43760

37

- 330

/ 1560

°F

 

 

 

 

 

C) LINEAR INPUTS

Read-out: keyboard programmable between -1999 and +9999.

Decimal point: programmable in any position

Burn out: the instrument shows the burn out condition as an underrange condition for 4-20 mA, 1-5 V and 2-10 V input types.

It shows the burn out condition as an underrange or an overrange condition (selectable by soldering jumper) for 0-60 mV and 12-60 mV input types. No indication are available for 0-20 mA, 0-5 V and 0-10 V input types.

22

LHL-1-NEUTRO.pmd

22

19/04/2004, 15.07

Image 25
Contents CN3271-add2.pmd 19/08/2004 OMEGAnet On-LineService Internet e-mail Info@omega.com Contents Mounting Requirements Screw Bracket PanelWithout RS-485 With RS-485 Dimensions and Rear Terminal BlocksPanel Cutout Wiring Guidelines RTD Input Linear Input MA, mV and V Inputs WiringRelay Outputs Logic Input for models with RS-485 onlyOUT 1 Class Use cupper conductors onlySerial Interface Inductive LoadsAA/A Power Line and grounding100 to 240 Vac 500 mA 250 100/240 V AC 125 mAHigh Low Limiter without RS-485 High Low Limiter with RS-485Configuration Procedure Configuration KEY FunctionsSerial Interface Protocol R7 = Alarm action on input fault R5 = Offset AdjustmentType Value R2 = Decimal Point PositionHi.Lo = High and low limit for special process C2 = Rearming ModeConstant Alarm Function = Rearm at Power-up Auto = Automatic rearm= Alarm configuration = Shutdown memoryExample for P2 = H.A.A.c P3 = Alarm ActionExample for P2 = H.L = Safety Lock Alarm Standby mask FunctionT1 = Timeout Selection Normal Display Mode Operating ModeFlashes when alarm is on IndicatorsNormal Display Mode to Operative Parameter Display Mode Operative Parameter Display ModeOperating Parameters Example 1 C1 = Hi and C2 = O Example 2 C1 = Hi and C2 = Limiter functionSerial LInk optional Alarm functionsDevice can be connected to a host computer via serial link Error Messages Error MessagesError List Dealing with Error MessagesPower consumption 8 VA General SpecificationsCommon mode rejection ratio Temperature Drift CJ excludedLinear Inputs Inputs ThermocoupleLogic Inputs AlarmOutputs OutputSerial Communication Interface Option MaintenanceDefault Operating Parameters List Default ParametersLHL-A-NEUTRO.pmd 19/04/2004 Second Seconds Appendix A.3 Appendix B Thermocouple Compensating Cable Color Codes Return Requests / Inquiries Data Acquisition