Liebert GXT3 user manual Options Tab

Page 10

6

Chapter 4 Tabs

Notes

1.For the GXT3 Dual-Inverter models, this sets the L1-N and the L2-N nominal voltage.

2.The L1-L2 voltage is dependent upon the phase angle of the input utility and is auto-detected when power is first applied.

3.For the GXT3 230 volt single inverter model, only those voltages supported by the UPS will be displayed.

L-N reverse detection

The L-N reverse detection is only for the 120V UPS. Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression, and surge suppression. The UPS checks the outlet when first plugged in.

Enable L-N reverse detection is checked

When the box of Enable L-N Reverse Detection (120V UPS only) is checked, alarm of L-N reverse will be enabled.

If the Line-Neutral is reversed or the ground is missing, the UPS will not start.

If a problem is detected after the UPS is started, the UPS will continue to operate, bu t the AC INPUT LED will flash.

In this situation, the improperly wired receptacles should be immediately repaired before the UPS is put into service.

Enable L-N reverse detection is unchecked

When the box of Enable L-N Reverse Detection (120V UPS only) is unchecked, alarm of L-N reverse will be disabled.

Frequence selection

The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems.

For typical applications

Auto Sensing – 50 or 60Hz – Bypass Enabled or Auto Sensing – 50 or 60Hz – Bypass Disabled should be selected according to the application.

The UPS will auto-sense the utility frequency when first plugged in and set the nominal frequency to match.

For some special applications

For some special applications, the UPS is required to be used as a frequency converter. In this application the following options are available:

Frequency Converter – 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled.

Frequency Converter – 50Hz – Bypass Disabled mode will provide 50Hz UPS output from any qualified commercial power. Frequency Converter – 60Hz – Bypass Disabled mode will provide 60Hz UPS output from any qualified commercial power.

Note

Frequency Converter – 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled mode disables the Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not be available and power will be removed from any load.

Audible alarm control

Enable Audible Alarm Control, if checked the audible alarms are enabled.

Enable Audible Alarm Control, if unchecked the audible alarms are disabled.

4.2 Options Tab

Select the Options Tab, as shown in Figure 4-3.

GXT3 Configuration Program User Manual

Image 10
Contents GXT3 Configuration Program Page Contents Page Introduction FeaturesRequirements Communicating With The UPS Connecting The USB CableStarting The Program  NoteOperation Read/Config UPS Settings OnlyChanging UPS Settings Requirements on the UPSChanges rejected Partial saveUPS Tab TabsOutput voltage selection Options Tab Auto-enable output automatically Battery TabDisable output manual restart only Default operation normally openBattery cabinets Low battery time warningAuto battery test time Auto battery testAbout Tab Window of About Tab