Liebert GXT3 user manual Changes rejected, Partial save

Page 8

4

Chapter 3 Operation

Note

At this time, if the UPS is already ON, you do not need to restart it.

Changes rejected

When the Apply or OK button is selected to transmit new settings on the UPS Tab or Options Tab, the UPS must be put in the Standby mode, or the changes will be rejected, and the error message will be displayed, as shown in Figure 3-2.

Figure 3-2 The changes are rejected

At this point, you should put the UPS to the Standby mode. If the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to place the UPS in Standby mode.

Partial save

If the UPS is not in the Standby mode, and changes from both the Battery Tab and the UPS Tab or Options Tab are selected, the UPS will only save the changes on the Battery Tab. The Partial Save message will be displayed, as shown in Figure 3-3.

Figure 3-3 Partial save

GXT3 Configuration Program User Manual

Image 8
Contents GXT3 Configuration Program Page Contents Page Requirements FeaturesIntroduction Connecting The USB Cable Starting The ProgramCommunicating With The UPS  NoteRead/Config UPS Settings Only Changing UPS SettingsOperation Requirements on the UPSChanges rejected Partial saveOutput voltage selection TabsUPS Tab Options Tab Battery Tab Disable output manual restart onlyAuto-enable output automatically Default operation normally openLow battery time warning Auto battery test timeBattery cabinets Auto battery testAbout Tab Window of About Tab