Liebert GXT3 Operation, Read/Config UPS Settings Only, Changing UPS Settings, Saving the changes

Page 7

Chapter 3 Operation

3

Chapter 3 Operation

This chapter details how to operate the program, including read/config UPS settings only and changing UPS settings.

3.1 Read/Config UPS Settings Only

This program can monitor the UPS settings while the UPS is operating in any mode. If this program is only used to read/config the present UPS settings, you do not need to use any buttons except the Cancel button to close the program .

3.2 Changing UPS Settings

To change the UPS settings, there are three conditions: canceling the settings , restore the settings and changing the settings.

3.2.1 Canceling The Settings

If you decide not to change the UPS settings after modifying the displayed settings, close the program using the Cancel button, and the settings are canceled.

3.2.2 Restore The Settings

If you decide to restore the UPS settings after modifying the displayed settings and prior to select OK or Apply button, select the Refresh button to restore the UPS settings to the existing values stored in the UPS.

3.2.3 Changing The Settings

Requirements on the UPS

All UPS settings can be changed when the UPS is in Standby mode (with AC input power available). Pay attention to the following two conditions:

Settings on the UPS Tab and Options Tab can only be changed with the UPS in Standby mode.

Settings on the Battery Tab can be changed with the UPS in Normal or Standby mode.

If the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to place the UPS in Standby mode. This will disconnect all power to the load.

Saving the changes

Changing any value or selecting/deselecting any setting in the configuration window will not immediately change the settings in the UPS. You may modify the displayed settings until you are satisfied with the new proposed changes. After that, you can save the values by selecting either the Apply or OK button.

The Apply button sends the new settings to the UPS without closing the program.

The OK button sends the new settings to the UPS and closes the program.

Whenever the value is successfully saved, the message will be displayed, as shown in Figure 3-1.

Figure 3-1 The changes are saved

GXT3 Configuration Program User Manual

Image 7
Contents GXT3 Configuration Program Page Contents Page Introduction FeaturesRequirements  Note Connecting The USB CableStarting The Program Communicating With The UPSRequirements on the UPS Read/Config UPS Settings OnlyChanging UPS Settings OperationPartial save Changes rejectedUPS Tab TabsOutput voltage selection Options Tab Default operation normally open Battery TabDisable output manual restart only Auto-enable output automaticallyAuto battery test Low battery time warningAuto battery test time Battery cabinetsWindow of About Tab About Tab
Related manuals
Manual 44 pages 44.14 Kb