Liebert 350VA to 1000VA AC Output Voltage Configuration, Voltage Regulation ±10% steady state

Page 3

127VAC nominal: single phase, 2-wire-plus-ground: 90 ─ 150 VAC (±3VAC), Buck compensation: 141VAC (±3VAC)

Boost1 compensation: 113VAC (±3VAC)

Boost2 compensation: 100VAC (±3VAC)

220VAC nominal: single phase, 2-wire-plus-earth: 155 ─ 270 VAC (±6VAC) Buck compensation: 243 VAC (±6VAC)

Boost1 compensation: 197 VAC (±6VAC)

Boost2 compensation: 174 VAC (±6VAC)

230VAC nominal: single phase, 2-wire-plus-earth: 163 ─ 282 VAC (±6VAC) Buck compensation: 254 VAC (±6VAC)

Boost1 compensation: 207 VAC (±6VAC)

Boost2 compensation: 183 VAC (±6VAC)

240VAC nominal: single phase, 2-wire-plus-earth: 171 ─ 291 VAC (±6VAC) Buck Compensation: 265 VAC (±6VAC)

Boost1 compensation: 215 VAC (±6VAC)

Boost2 compensation: 191 VAC (±6VAC)

B.Frequency: The UPS automatically senses the input frequency and operates within the following frequency specifications without drawing power from the batteries.

50 Hz Applications: 46.5 ─ 53.5 Hz (±0.1 Hz)

60 Hz Applications: 56.5 ─ 63.5 Hz (±0.1 Hz)

C.Surge Protection: The 120 VAC units can withstand input surges of up to 570J without damage per criteria listed in IEEE C62.41, Category A, Level 3. The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000-4-5, Level 3, Criteria A.

D.Input Connections: The 120 VAC units have an attached input cord 6.0 feet (1.8 meters) in length, measured between the inside edges of the connectors. The attached input cord has a NEMA 5-15 plug.

1.3.3.2 AC Output

A.Voltage Configuration:

120 VAC units: 110/120/127 VAC, 60/50 Hz, single-phase, 2-wire-plus-ground. 120VAC ± 8% (Battery mode)

230 VAC units: 220/230/240 VAC, 50/60 Hz, single phase, 2-wire-plus-earth.

230 VAC ±8% (Battery mode)

B.Voltage Regulation: ±10% steady state.

C.Frequency Regulation: +0.1Hz synchronized to utility / mains. +0.5Hz free running or on battery operation.

D.Load Power Factor Range: 0.6 lagging to 1.0 (unity).

E.Inverter Overload Capability: Overload Warning (visual and audible alarms) occurs between 100%─109% of rated capacity, continuous duty. Shutdown occurs at the following

levels:

>110 ─ 120%; after 120 seconds (Normal mode)

 

>120 ─ 150%; after 15 seconds (Normal mode)

 

>150% - short-circuit; after 5 seconds (Normal mode)

 

>110%; after 2 cycles (Battery mode)

PowerSure PSA

3

Guide Specification

350 – 1000VA

 

SL-23271 8/03

Image 3
Contents Modes of Operation General SummaryStandards System DescriptionDesign Requirements OutputPerformance Requirements 1.3.3.1 AC Input to UPS Voltage Regulation ±10% steady state AC Output Voltage ConfigurationEnvironmental Conditions User Accessories and Packaging WarrantyProduct Fabrication Unit Unit Dimensions VAC UnitsWeight Quality AssuranceBi-Directional Converter DC Protection Battery RechargeBattery Over-Discharge Protection Bi-Directional Converter 2.2.2.1 GeneralUnit VAC Units Communications