GE DEH-40417 manual Location of SCRs on size M, Z, N ASTAT-IBP

Page 11

ASTAT ®-IBP Plus Service Instructions

SCR Module Replacement (Sizes M, Z,

and N)

This procedure requires the following tools and materials:

#2 Philips-head screwdriver, 3/16" Allen wrench, torque wrench

Scotchbrite or equivalent abrasive

Mild solvent to clean mounting surfaces

Electrolube 2GX or equivalent thermal grease

1.Loosen the screws holding the MOVs and bus bars to the SCR Module to be replaced, shown in Figure 14, and remove the MOVs and bus bars.

2.Remove the mounting screws at each end of the SCR Module, then lift out the Module. Retain all parts and hardware removed from the SCR Module for reassembly with the replacement Module.

3.Clean the heat sink surface of the replacement Module with a fine abrasive, such as Scotchbrite. Remove all particles from the heat sink surface and wipe the SCR mounting surface with a mild solvent. Apply a light coat of thermal grease, such as Electrolube 2GX to both the SCR and heat sink surfaces.

4.Place the contact face of the SCR Module on the mating heat sink surface. Move the Module back and forth several times to distribute the thermal grease evenly over the contact surfaces.

5.Attach the SCR Module to the heat sink with the screws removed earlier. Tighten the screws to 44 in- lb.

6.Reattach the bus bars and MOVs to the SCR Module with the screws removed earlier. Tighten the screws to 80 in-lb.

Figure 14. Location of SCRs on size M, Z, N ASTAT-IBP.

Prices and data subject to change without notice.

7

Image 11
Contents Astat -IBP Plus Solid State Starters Page AS Used in this Publication Astat -IBP Plus Service Instructions Table of Contents Cover Removal and Replacement Astat -IBP Plus Service InstructionsAstat -IBP Plus Service Instructions Logic Board Replacement Location of the Power Supply Board Gate lead connections for sizes K, L, and Y Board Removing the SCR module Location of SCRs on size M, Z, N ASTAT-IBP Disconnecting the SCR load side Removing the busbar mounting bolt Forth several times to evenly distribute the grease on PCB Astat -IBP Plus Service Instructions Troubleshooting GuideQI3P,Q,R,SDP Astat -IBP Plus Service Instructions Renewal Parts ListPage GE Industrial Systems