GE DEH-40417 manual Removing the busbar mounting bolt

Page 13

ASTAT ®-IBP Plus Service Instructions

SCR Module Replacement (Size S)

This procedure requires the following tools and materials:

9 /16" wrench, 11/16" wrench, 3/16" Allen wrench, torque wrench

Scotchbrite or equivalent abrasive

Mild solvent to clean mounting surfaces

Electrolube 2GX or equivalent thermal grease

1.Disconnect the control wiring harness for the SCRs to be replaced. If necessary, disconnect the wiring harness of the CTs.

2.Remove the bolt holding the busbars connected to the blocks on the load and line sides of the SCR Module, as shown in Figure 18.

3.Remove the bolt holding the CT, the threaded stud, and the load-side busbar from the Module.

4.Remove the bolts holding the load-side lug in place. Remove the lug.

5.Remove the L-shaped busbar and CT, if applicable, from the assembly, as shown in Figure 19.

6.Remove the four screws holding the SCR Module to the mounting plate, as shown in Figure 20.

Figure 18. Removing the busbar mounting bolt.

Figure 19. Removing the L-shaped busbar.

Figure 20. Removing the SCR mounting screws.

Prices and data subject to change without notice.

9

Image 13
Contents Astat -IBP Plus Solid State Starters Page AS Used in this Publication Astat -IBP Plus Service Instructions Table of Contents Cover Removal and Replacement Astat -IBP Plus Service InstructionsAstat -IBP Plus Service Instructions Logic Board Replacement Location of the Power Supply Board Gate lead connections for sizes K, L, and Y Board Removing the SCR module Location of SCRs on size M, Z, N ASTAT-IBP Disconnecting the SCR load side Removing the busbar mounting bolt Forth several times to evenly distribute the grease on PCB Astat -IBP Plus Service Instructions Troubleshooting GuideQI3P,Q,R,SDP Astat -IBP Plus Service Instructions Renewal Parts ListPage GE Industrial Systems