2 Site Preparation and Unpacking
This chapter includes the following sections:
●“Site Requirements for the Sentriant AG Appliance” on page 11
●“Unpacking the Sentriant AG Appliance” on page 12
Site Requirements for the Sentriant AG Appliance
The Sentriant AG200 appliance can be
Locate the system away from heat sources and in an area that provides unobstructed air flow to the chassis cooling vents. The chassis intake ambient air temperature should not exceed 95 ºF (35 ºC) or drop below 41ºF (5º C).
CAUTION
Do not place a monitor or other object on top of the system. The mounting brackets and chassis cover are not designed to support additional weight.
Make sure that the voltage and frequency of the power source matches the electrical ratings of the
Sentriant AG appliance, and that the building and/or power source provides overload protection.
Operating humidity should be kept between 10% and 95% relative humidity (noncondensing).
In regions that are susceptible to electrical storms, we recommend that you plug your system into a surge suppressor.
Rack Ventilation Requirements
●Make sure that there is a minimum of 3 inches of airspace at the back of the chassis.
●
●
●If you are installing the Sentriant AG appliance in enclosed racks with
●Chassis intake ambient air temperature should not exceed 95º F (35º C).
Sentriant AG200 Hardware Installation Guide | 11 |
|
|