Guaranteed Uninterruptible Power

System

TECHNICAL SPECIFICATIONS

 

 

Model

UP1200

Capacity (VA)

1200VA

Capacity (Watts)

670W

Input

 

Input Voltage Range

100Vac – 140Vac

Frequency Range

57 – 63 Hz

Output

 

On Battery Output Voltage

Simulated Sine Wave at 120Vac +/- 5%

On Battery Output Frequency

60 Hz +/- 1%

Transfer Time (Typical)

4ms

Overload Protection

On Utility: Circuit Breaker, On Battery: Internal Current Limiting

Surge Protection and Filtering

 

Lightning / Surge Protection

Yes

Internet Ready (DSL / Phone /

RJ11/RJ45 (One In/One Out)

FAX / Modem Protection)

 

Physical

 

Total # of UPS Receptacles

4 for UPS, 4 for Surge

Maximum Dimensions

31.0cm*14.1cm*18.1cm

Weight

12.3kg

Battery

 

Sealed Maintenance Free Lead

12V / 7.2AHx2

Acid Battery

 

Replaceable

Yes

Typical Recharge Time

8 Hours

Warning Diagnostics

 

Indicators

Power On, Using Battery, Wiring Fault

Audible Alarms

On Battery, Low Battery, Overload

Environmental

 

Operating Temperature

+32°F to 95°F ( 0°C to 35°C )

Operating Relative Humidity

25% to 85% Non Condensing

Communication

 

PowerPanelTM Software

Windows 95/98/ME/NT/2000/XP

Management

 

Self-Test

Yes

Auto-Charger

Yes

Auto-Restart

Yes

USB

Yes

 

9

Image 9
Contents User’s Manual Utility Series UPS Table of Contents Important Safety Warnings Basic Operation Installing Your UPS SystemPower Switch BA-UP1200 for UP1200 Battery Replacement and StorageStorage Problem Possible Cause Solution TroubleshootingModel UP1200 Technical SpecificationsAlarm Battery Fault Breaker Definitions for Illuminated LED IndicatorsRegistration Limited Warranty Limited Warranty and Power Control GuaranteeMaking a Limited Warranty Claim Exclusive Remedies Under Limited WarrantyCyberPower’s Duties Making a Power Control Guarantee ClaimPage Exclusion of Consequential and Other Damages