AUTOMATIC TRANSFER SWITCH
FOR EXTERNAL POWER CONNECTIONS
| Normal, Emergency |
| Normal, Emergency | ||
| & Load Terminals |
| & Load Terminals | ||
Switch Size | Cables | Range of | Switch Size | Cables | Range of |
Amps | per Pole | Wire Sizes | Amps | per Pole | Wire Sizes |
|
|
|
|
|
|
| #8 to 3/0 AWG | 800/1000/1200 | 4 | #2 AWG to 600 MCM | |
1 | #6 AWG to 250 MCM | 1600 |
|
| |
260 |
| #6 AWG to 350 MCM | 2000 | 8 | 600 MCM |
400 |
| #4 AWG to 600 MCM | 3000 | ||
|
|
| |||
600 | 2 | #2 AWG to 600 MCM | 4000 |
|
|
NOTES:
*Line and load terminals are located in rear and arranged for bus bar connection.
1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes and number of conductors per pole.
2. Fully rated solid neutral (3x standard normal power connector) provided when required by system voltage.
3. Normal and emergency may be ordered inverted on any switch. Load may be inverted
4. Lug adapters for
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
©2012 Caterpillar
All Rights Reserved.
Printed in U.S.A.
8 |