CAT LEHE4651-04 manual CAT CTS Series of Automatic Transfer Switches, Amps, Drive Mechanism

Page 2

AUTOMATIC TRANSFER SWITCH

THE CAT CTS SERIES OF AUTOMATIC

TRANSFER SWITCHES

The Cat CTS Series power contactor Type transfer switch makes use of a fully programmable/configurable microprocessor-based controller to allow the utmost in application flexibility. Further, the CTS Series is offered in a wide array of configurations enabling it to meet the needs of even the most highly critical load.

Available configurations include:

40-4000 Amps:

CTS Automatic Transfer Switches

CTSD Delayed Transition Transfer Switches

CTSM Manual Transfer Switches

100-4000 Amps:

CTSCT Closed Transition Transfer Switches

CBTS Automatic Transfer/Bypass Switches

CBTSD Delayed Transition Bypass Switches

CBTSCT Closed Transition Bypass Switches

All CTS products meet or exceed industry requirements to allow specification and installation with confidence.

UL 1008 listed through 480 VAC

CSA C22.2 No. 178 listed through 600 VAC

IEC 947-6-1 listed through 480 VAC

Codes and Standards NFPA 70, 99, 101, 110 NEC 517, 700, 701, 702 IEEE 446, 241 NEMA ICS2-447

Controls tested in accordance with: IEEE 472 (ANSI C37.90A) EN55022 Class B (CISPR 22)

(Exceeds EN55011 & MILSTD 461 Class 3) EN61000-4-2 Class B (Level 4) EN61000-4-3 (ENV50140) 10v/m EN61000-4-4

EN61000-4-5, IEEE C62.41 EN61000-4-6 (ENV50141) EN61000-4-11

Equipment (Controls and Power Section) Seismic Test Qualified to:

IBC-2003 IEEE-693-2005

Enclosures meet the requirements of: UL 508, UL 50, ICS 6, ANSI C33.76 and NEMA 250

Quality System:

ISO 9001 Registered

LEHE4651-04

2

This ruggedly built family of power contactor switches has been specifically designed for transfer switch duty with dependability, versatility and user friendliness of prime concern.

The CTS power panel components, consisting of power switching contacts, drive mechanism and terminal lugs, are mounted on a specially formed backplane. Logic devices including microprocessor control auxiliary time delays and special accessory equipment are assembled on the door for ease of maintenance and separation from the power section. They are connected with a numbered wiring harness equipped with a disconnect plug that allows isolation of the control panel for maintenance.

CTS SERIES METHOD OF OPERATION When the normal source fails or the voltage drops to a predetermined point (usually 80% of nominal), if required, a circuit is closed to start the engine generator set. When the emergency source reaches 90% of rated voltage and 95% of rated frequency, the drive solenoid is energized through the emergency coil control relay, causing the main contacts to disconnect the load from the normal source and connect it to the emergency source. After the drive solenoid has completed its electrical stroke and is seated, the emergency coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the emergency position. When normal voltage is restored to a predetermined point (usually 90% of nominal), the control voltage sensing energizes. The normal side coil relay closes, and after the drive solenoid has completed its electrical stroke and is seated, the coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the normal position.

DRIVE MECHANISM

All CTS switches employ the simple “over-center” principle to achieve a mechanically locked position in either normal or emergency and a high speed drive assures contact transfer in 100 ms or less. High contact pressure and positive mechanical lock allow for high withstand and closing ratings, far exceeding UL requirements.

Image 2
Contents Design and Construction Features FeaturesPerformance Features Electrical RatingsDrive Mechanism CAT CTS Series of Automatic Transfer SwitchesAmps Transferring Large Motor Or Highly Inductive Loads Neutral SwitchingSafe Manual Operation CTS Series ATSOptional Packages Standard Features Mstd PackageFeature Function CTS Series Accessory Definitions CTS Series Accessory DefinitionsCTS Series Accessory Group Matrix SW2 S5PSW1 SW3CTS Series Dimensional Specifications Application NotesNormal, Emergency