FieldServer FS-8704-06 Driver Specific FieldServer Parameters, 65535, Server Side Connections

Page 9

FS-8704-06 BACnet IP Driver Manual

Page 9 of 24

5.Configuring the FieldServer as a BACnet IP Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet/IP Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet/IP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Driver Specific FieldServer Parameters

Section Title

 

 

Bridge

 

 

Column Title

Function

Legal Values

Title

FieldServer name

Text

Network_number*

Specify a unique network number

1-65535

if there are multiple virtual Server

5

 

nodes.

 

 

Example

 

 

//FieldServer Driver specific parameters Bridge

Title,

 

Network_Number

BACnet Server,

 

6

5.2.Server Side Connection Descriptors

 

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

Function

 

Legal Values

 

Adapter

Adapter Name

 

N1, N26

 

Protocol

Specify protocol used

 

BACnet_IP

 

Connection_Type*7

Specify if this Connection should act as a BBMD

 

 

 

Server on the network. Refer to Appendix B.5 for

BBMD

 

 

more information.

 

 

 

 

IP_Port*

Specify the UDP port that will be used to

Any legal IP port value

 

communicate with other BACnet Client devices.

(1 - 65535); 47808

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

// Server Side Connections

 

 

 

 

Connections

 

 

 

 

 

Adapter,

Protocol,

Connection_Type

 

 

N1,

Bacnet_IP,

BBMD

 

 

6Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware. 7 BBMD only runs on N1 on an X30.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 9
Contents Applicability & Effectivity Driver Manual FS-8704-06 BACnet/IPTable of Contents FS-8704-06 BACnet IP Driver Manual BACnet IP Description HardwareProvided by the Supplier of 3rd Party Equipment DescriptionFS-8704-06 BACnet IP Driver Manual Hardware Connections Data Arrays/Descriptors Client Side Node Descriptors Driver Related Map Descriptor Parameters FieldServer Related Map Descriptor ParametersTiming Parameters AI, AO, AV, BI, BO, BV, MIFS-8704-06 BACnet IP Driver Manual Map Descriptor Example65535 Driver Specific FieldServer ParametersServer Side Connection Descriptors Server Side ConnectionsServer Side Map Descriptors FieldServer Specific Map Descriptor ParametersMO, MV Driver Specific Map Descriptor ParametersFS-8704-06 BACnet IP Driver Manual Map Descriptor Example Page Appendix B.2. BACnet Priority Arrays Appendix B.4. IP Address Issues related to BACnet IP Appendix B.6. Using BbmdAppendix B.5. Network number FS-8704-06 BACnet IP Driver Manual Bbmd Block Diagram FS1FS2 Daao UINT16 Daai UINT16Dadi Dado47808 Nodes NodeName NodeID Protocol Server-1 11276 BacnetIP Dastatetxt Dastatetxt ByteAppendix C.2 BACnet Specific Statistics FS-8704-06 BACnet IP Driver Manual Appendix D. Units KVA KvarMvar PSI GPMVAR