FieldServer FS-8704-06 instruction manual Appendix B.4. IP Address Issues related to BACnet IP

Page 15

FS-8704-06 BACnet IP Driver Manual

Page 15 of 24

The Map Descriptor property must be Present_Value.

Appendix B.4. IP Address Issues related to BACnet IP

It is not necessary to configure the IP address of the Server node in the Client Side Node Descriptor in the configuration file since the BACnet Client will automatically discover the IP address based on the Node_ID supplied. It is still necessary for the FieldServer itself to have a valid IP address, however. Please refer to the FieldServer Utilities Manual for instructions on changing the FieldServer IP address.

Appendix B.5. Network number

The default Network number of a FieldServer is 5. In order to ensure communication between the BACnet Client and all Servers on a BACnet network, however, it may be necessary to assign a unique network number to each FieldServer.

A unique network number will need to be assigned if both of the following conditions are true:

The FieldServer has multiple BACnet Server nodes.

There is more than one FieldServer on a network which includes multiple BACnet nodes.

To override the FieldServer’s default network number 5, refer to Section 5.1

Appendix B.6. Using BBMD

BACnet/IP requires that a BBMD be defined on every subnet for cross-router communications. The FieldServer can act as a BBMD for the subnet that it resides on. Setting the Connection_Type to BBMD will enable this functionality on the FieldServer. Note that BBMD operation is not required if there is already another BBMD on the network.

Setting up a Broadcast Distribution Table (BDT)

The FieldServer supports two methods of updating its internal broadcast distribution table.

Trane’s Tracer Summit IP Validation utility can be used directly to upload and download a Broadcast Distribution Table.

The Broadcast Distribution Table can be configured using the bdt.ini file. The following file must be created and downloaded to the FieldServer using the Ruinet “Download Configuration” command.

//

 

 

BBMD IP_Address,

BBMD port,

BBMD subnet Mask

24.90.48.179,

47808,

255.255.255.255

64.80.115.156,

47808,

255.255.255.255

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 15
Contents Applicability & Effectivity Driver Manual FS-8704-06 BACnet/IPTable of Contents Description HardwareFS-8704-06 BACnet IP Driver Manual BACnet IP Description Provided by the Supplier of 3rd Party EquipmentFS-8704-06 BACnet IP Driver Manual Hardware Connections Data Arrays/Descriptors Client Side Node Descriptors AI, AO, AV, BI, BO, BV, MI FieldServer Related Map Descriptor ParametersDriver Related Map Descriptor Parameters Timing ParametersFS-8704-06 BACnet IP Driver Manual Map Descriptor ExampleServer Side Connections Driver Specific FieldServer Parameters65535 Server Side Connection DescriptorsServer Side Map Descriptors FieldServer Specific Map Descriptor ParametersMO, MV Driver Specific Map Descriptor ParametersFS-8704-06 BACnet IP Driver Manual Map Descriptor Example Page Appendix B.2. BACnet Priority Arrays Appendix B.4. IP Address Issues related to BACnet IP Appendix B.6. Using BbmdAppendix B.5. Network number FS-8704-06 BACnet IP Driver Manual Bbmd Block Diagram FS1FS2 Dado Daai UINT16Daao UINT16 Dadi47808 Nodes NodeName NodeID Protocol Server-1 11276 BacnetIP Dastatetxt Dastatetxt ByteAppendix C.2 BACnet Specific Statistics FS-8704-06 BACnet IP Driver Manual Appendix D. Units KVA KvarMvar PSI GPMVAR