FieldServer FS-8704-14 instruction manual Appendix A.6.1 FieldServer Configuration File

Page 22

 

 

FS-8704-14 EtherNet/IP Manual

 

Page 22 of 30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appendix A.6.1.

FieldServer Configuration File

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

//

 

 

 

 

 

Data_Arrays

 

 

 

 

 

Data_Array_Name

,Data_Format

,Data_Array_Length

 

 

 

DA_Read

,Float

,50

 

 

 

DA_Write

,Float

,50

 

 

 

 

 

 

 

//

Client Side Connections

 

//

 

 

Connections

 

Adapter

,Protocol

N1

 

,Ethernet/IP

//

Client Side Nodes

 

 

 

//

 

 

 

 

Nodes

 

 

 

Node_Name

,IP_Address

,Protocol

,Adapter

EIP_01

,192.168.1.9

,Ethernet/IP

,N1

 

 

 

 

 

These are the PLC Tag names that will be accessed in the PLC. The names must match the PLC tag name exactly.

Appendix A.3 lists the paths for specific devices

 

// Client Side Map Descriptors

 

 

 

 

 

 

 

 

 

 

//

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name

,Scan_Interval

,Data_Array_Name

,Data_Array_Offset

,EIP_CON_TYP

,Node_Name

,Function

,EIP_SERVICE

,EIP_PATH

,EIP_TAG_NAME

,Length

 

PLC_TO_FIELDSERVER

,0.1

,DA_Read

,0

,EXPLICIT

,EIP_01

,Rdbc

,DATA_TABLE_READ

,1 0

,FS_Status

,20

 

FIELDSERVER_TO_PLC

,0.1

,DA_Write

,0

,EXPLICIT

,EIP_01

,Wrbc

,DATA_TABLE_WRITE

,1 0

,FS_Control

,20

 

 

 

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 22
Contents Driver Manual FS-8704-14 EtherNet/IP Table of Contents Appendix C. Error Messages Odva Status Supplied by FieldServer Technologies for this driverHardware Connections Configuring the Fieldserver AS AN ETHERNET/IP Client Data Arrays/DescriptorsClient Side Connection Descriptions Client Side Node Descriptors3There can be 200 Floats FS-8704-14 EtherNet/IP ManualPage 9 Driver Related Map Descriptor Parameters Pccc Timing ParametersMap Descriptor Example 2 Data Table Messages Map Descriptor Example 1 Unconnected MessagesMap Descriptor Example 3 Pccc Messages Configuring the Fieldserver AS AN ETHERNET/IP Server Server Side Connection DescriptorsServer Side Node Descriptors3 FS-8704-14 EtherNet/IP ManualPage 14 FS-8704-14 EtherNet/IP ManualPage 15 SMDPRO01 Appendix A.2. FieldServer as an Adapter and Scanner Appendix A.4. Setting the Data Type for stored dataAppendix A.1. General Notes Appendix A.3. Common PathsEipservice Eiptagname Step Read Message Block FS-8704-14 EtherNet/IP Manual Appendix A.6.1 FieldServer Configuration File FieldServer as a Client SSSSINT3 Attributes Supported Services Supported Appendix A.8. Classes and Attributes SupportedAttributes Supported Services Supported Appendix A.9. Error Codes Attempt to change number of array dimensions Appendix B.1. Firmware Update Downloading Appendix B.3. FieldServer not recognised by RSlinxAppendix C. Error Messages