4CONFIGURING THE FIELDSERVER AS AN ETHERNET/IP CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with an EtherNet/IP Server.

4.1Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for EtherNet/IP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

Section Title

 

 

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

Data_Array_Name

 

 

Provide name for Data Array

 

 

Up

to 15

alphanumeric

 

 

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Provide data format. Each Data Array

 

 

Float,

Bit,

UInt16, SInt16,

 

Data_Array_Format

 

 

 

 

Packed_Bit,

Byte,

 

 

 

can only take on one format.

 

 

 

 

 

 

 

 

Packed_Byte, Swapped_Byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Data Objects. Must be larger

 

 

 

 

 

 

Data_Array_Length

 

 

than the data storage area required by

 

1-10,000

 

 

 

 

the Map Descriptors for the data being

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

placed in this array.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

//

Data Arrays

 

 

Data_Arrays

 

 

Data_Array_Name ,Data_Format

,Data_Array_Length

DA_AI_01

,UInt16

,200

DA_AO_01

,UInt16

,200

DA_DI_01

,Bit

,200

DA_DO_01

,Bit

,200

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 6
Contents Driver Manual FS-8704-14 EtherNet/IP Table of Contents Appendix C. Error Messages Odva Status Supplied by FieldServer Technologies for this driverHardware Connections Configuring the Fieldserver AS AN ETHERNET/IP Client Data Arrays/DescriptorsClient Side Connection Descriptions Client Side Node Descriptors3There can be 200 Floats FS-8704-14 EtherNet/IP ManualPage 9 Driver Related Map Descriptor Parameters Pccc Timing ParametersMap Descriptor Example 1 Unconnected Messages Map Descriptor Example 2 Data Table MessagesMap Descriptor Example 3 Pccc Messages Configuring the Fieldserver AS AN ETHERNET/IP Server Server Side Connection DescriptorsServer Side Node Descriptors3 FS-8704-14 EtherNet/IP ManualPage 14 FS-8704-14 EtherNet/IP ManualPage 15 SMDPRO01 Appendix A.2. FieldServer as an Adapter and Scanner Appendix A.4. Setting the Data Type for stored dataAppendix A.1. General Notes Appendix A.3. Common PathsEipservice Eiptagname Step Read Message Block FS-8704-14 EtherNet/IP Manual Appendix A.6.1 FieldServer Configuration File FieldServer as a Client SSSSINT3 Attributes Supported Services Supported Appendix A.8. Classes and Attributes SupportedAttributes Supported Services Supported Appendix A.9. Error Codes Attempt to change number of array dimensions Appendix B.1. Firmware Update Downloading Appendix B.3. FieldServer not recognised by RSlinxAppendix C. Error Messages