FieldServer FS-8700-59 instruction manual Data Arrays

Page 10

FS-8700-59 Canatal Sachnet

Driver Manual

5.Configuring the FieldServer as a Canatal Satchnet Protocol Driver Server

For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Canatal Satchnet Protocol Driver Client (Master)

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Canatal Satchnet Protocol Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

 

Note that in the tables,

* indicates an optional parameter, with the bold legal value being the

 

default.

 

 

5.1 Data Arrays

 

 

 

 

 

 

 

Section Title

 

 

 

Data_Arrays

 

 

 

Column Title

Function

Legal Values

 

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

 

 

characters

 

Data_Format

Provide data format. Each data array can only

FLOAT, BIT, UInt16, SInt16,

 

 

take on one format.

Packed_Bit, Byte,

 

 

 

Packed_Byte, Swapped_Byte

 

Data_Array_Length

Number of Data Objects. Must be larger than

1-10,000

 

 

the data storage area required for the data

 

 

 

being placed in this array.

 

 

 

 

 

Example

//Data Arrays

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length

DA_AI_01,

UInt16,

200

DA_AO_01,

UInt16,

200

DA_DI_01,

Bit,

200

DA_DO_01,

Bit,

200

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 8

Image 10 Contents
FS-8700-59 Canatal Satchnet Driver Table of Contents Provided by user Supplied by FieldServer Technologies for this driverRS-485 connection adapter Driver Manual Canatal Device UTP or similar cable with RJ11 adapterInterconnecting Cable Characteristics Hardware ConnectionsData Arrays Column Title Function Legal Values Client Side Connections Client Side NodesDriver Specific Map Descriptor Parameters Client Side Map DescriptorsFieldServer Specific Map Descriptor Parameters Timing ParametersMap Descriptor Example DEV23COOL AnaoutTBL05DATA ,0 Rdbc , DEV11 Data Arrays Server Side Connections Server Side NodesServer Side Map Descriptors DEV11TBL5 Driver Notes Canatal Device Data TablesSeries Data Format Max Read Description Troubleshooting That the device is not functioning correctly Error. Poll%d/Response%d Stns Not EqualError. Poll%d/Response%d Tables Not Equal CANA#15