Appendix B. Troubleshooting tips

Appendix B.1. Connection Tips & Hints

Communication errors will be experienced if the port is disabled at the panel. Please check the Notifier Manuals on how to enable the panel port connected to the FieldServer and ensure that it is set to 80 columns NO supervision.

If connecting the Panel to one of the FieldServer RS-232 ports causes the FieldServer to reboot, then an Optical Isolator is required to balance ground potential problems.

Appendix B.2. Networking Tips

By default FieldServer does not take any action on receiving a “SYSTEM RESET”. Normally when a Node initiates “SYSTEM RESET” by pressing the “RESET” button on the Panel, the panel sends an individual “CLEAR” message for every point, it clears in its memory area. The FieldServer therefore waits for the “CLEAR” message to clear a specific bit in its memory for a particular Node or for the “SYSTEM NORMAL” message to clear all bits in its memory for every Node. Use Clear_on_Reset parameter if required.

It may be advisable to configure the Notifier panel to suppress less important “Supervisory” or “Trouble” messages which could prevent the generation of “SYSTEM NORMAL” messages. Consult Notifier for this configuration or recommendation.

Ensure that every Node is working with a printer or HyperTerminal, before calling FieldServer for Support.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com

Image 20
Contents Driver Manual FS-8700-130 Notifier NCA2-NFS2-3030 Effective for all systems manufactured after JanuaryTable of Contents Max Nodes Supported Supplied by FieldServer Technologies for this driverFS-8700-130 Notifier NCA2/NFS-3030 Manual TB5 CRT CRX CTXTB5 Printer PRX PTXHardware Connection Tips / Hints Panel Status Memory Mapping Active EventsMemory Type NodeTrouble Data Arrays/Descriptors ExampleClient Side Connection Descriptions Client Side Node DescriptorsDriver Related Map Descriptor Parameters Yes ,NoMap Descriptor Example Standard example FS-8700-130 Notifier NCA2/NFS-3030 Manual Fire Alarm Cleared Alarm Security Cleared SecurityAlarm Life Life Critical Cleared Alarm Critical Alarm Medical Cleared MedicalAppendix A.2. System Trouble Messages Remote Display 21 Trouble Analog Output 1 Trouble Remote Display 8 no Answer Appendix A.3. Node Status Appendix A.4. FieldServer SynchronizationAppendix A.5. Driver Limitations and Exclusions Appendix B.1. Connection Tips & Hints Appendix B.2. Networking TipsError Description Action OFFFYI