4CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2/NFS2-3030 CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to receive information from a Notifier Panel.

4.1Panel Status - Memory Mapping

The primary purpose of this driver is to record the status of devices connected to the Notifier panel by interpreting the text messages sent to the printer or CRT port. Not all messages will be interpreted, as many messages do not directly pertain to device status, or are not currently supported. The following subset of event messages is recognized:

Active Events:

FIRE ALARM

SECURITY ALARM (LIFE)

LIFE CRITICAL ALARM

MEDICAL EMERGENCY

SECURITY ALARM

CRITICAL PROCESS

SUPERVISORY

TROUBLE/ FAULT

DISABLED

PREALARM

ACTIVE

ON/ OFF

This Driver divides the memory into various types. Each location in each memory type is assigned an address. It is therefore possible to map an address to a particular offset in a Data Array and make it accessible for reading by other connected devices. The address structure is provided in Table 1.

Most of these addresses will only contain binary information to represent an active or inactive state.

Where multiple troubles are associated with a single device the addressed register corresponding to that device will be incremented as a counter for each trouble message and decremented when a trouble is cleared. These addresses should preferably be stored in SINT16 format in the Data Array.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com

Image 6
Contents Driver Manual FS-8700-130 Notifier NCA2-NFS2-3030 Effective for all systems manufactured after JanuaryTable of Contents Supplied by FieldServer Technologies for this driver FS-8700-130 Notifier NCA2/NFS-3030 ManualMax Nodes Supported TB5 Printer TB5 CRTCRX CTX PRX PTXHardware Connection Tips / Hints Panel Status Memory Mapping Active EventsMemory Type NodeTrouble Data Arrays/Descriptors ExampleClient Side Connection Descriptions Client Side Node DescriptorsDriver Related Map Descriptor Parameters Yes ,NoMap Descriptor Example Standard example FS-8700-130 Notifier NCA2/NFS-3030 Manual Alarm Life Life Critical Cleared Fire Alarm ClearedAlarm Security Cleared Security Alarm Critical Alarm Medical Cleared MedicalAppendix A.2. System Trouble Messages Remote Display 21 Trouble Analog Output 1 Trouble Remote Display 8 no Answer Appendix A.3. Node Status Appendix A.4. FieldServer SynchronizationAppendix A.5. Driver Limitations and Exclusions Appendix B.1. Connection Tips & Hints Appendix B.2. Networking TipsError Description Action OFFFYI