FieldServer NCA2-NFS2-3030, FS-8700-130 Appendix A.5. Driver Limitations and Exclusions

Page 19

FS-8700-130 Notifier NCA2/NFS-3030 Manual

Page 19 of 22

 

 

Appendix A.5. Driver Limitations and Exclusions

Zone information will not be recorded.

To synchronize the FieldServer with the panel, connect the running FieldServer and press the “System Reset” button on the panel. All current events will be re-sent to the FieldServer.

The port must be enabled on the unit and set to 80 columns with NO supervision

All data related to non-event driven reports will not be recorded by the FieldServer

This driver was written as a subset of NFS2-3030/NCA-2EIA-232 Protocol & Data Formats 53219 Rev A 1/3/2008. Any changes or additions by Notifier will not be reflected in this driver unless specifically revised.

This driver will not record information about zone status that is incorporated with point status messages.

There can only be one panel connected to any given FieldServer port.

This driver records data as presented to the printer/CRT port by the Notifier panel, and can only be as accurate as this data.

The driver cannot send messages to the Notifier panel.

Driver will clear any data on “System Normal” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Normal. By default Clear_on_Normal is “yes”.

Driver will clear any Node data on “System RESET” only if this data is previously set by driver and is not yet cleared by “Cleared” message and is configured to Clear_on_Reset. By default Clear_on_Reset is “no”.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com

Image 19
Contents Effective for all systems manufactured after January Driver Manual FS-8700-130 Notifier NCA2-NFS2-3030Table of Contents FS-8700-130 Notifier NCA2/NFS-3030 Manual Supplied by FieldServer Technologies for this driverMax Nodes Supported PRX PTX TB5 CRTCRX CTX TB5 PrinterHardware Connection Tips / Hints Active Events Panel Status Memory MappingMemory Type NodeTrouble Example Data Arrays/DescriptorsClient Side Node Descriptors Client Side Connection DescriptionsYes ,No Driver Related Map Descriptor ParametersMap Descriptor Example Standard example FS-8700-130 Notifier NCA2/NFS-3030 Manual Alarm Critical Alarm Medical Cleared Medical Fire Alarm ClearedAlarm Security Cleared Security Alarm Life Life Critical ClearedAppendix A.2. System Trouble Messages Remote Display 21 Trouble Analog Output 1 Trouble Remote Display 8 no Answer Appendix A.4. FieldServer Synchronization Appendix A.3. Node StatusAppendix A.5. Driver Limitations and Exclusions Appendix B.2. Networking Tips Appendix B.1. Connection Tips & HintsOFF Error Description ActionFYI