Multiply: AC AMPS X 110 (AC voltage) = WATTS

This formula yields a close approximation of the continuous load of your appliance.

Multiply: WATTS X 2 = Starting Load for most appliances

This formula yields a close approximation of the starting load of most appliances. Exceptions are motorized appliances such as pumps, freezers and air conditioners. These appliances can have startup loads of up to eight times the rated watts.

5

Image 5
Contents Page Higher Wattage Inverter May Be Required WelcomeAppliance Cautions Getting Started Page Front Panel EN900 / EN1100 LCD DiagramRear Panel EN900 / EN1100 Determining the DC Power RequirementsSizing the Battery Bank Cable Gauges Mounting the Inverter Connecting the InverterTelevision and Audio Suggestions OperationPage Problem Inverter is Shut Down Best use of Battery PowerTroubleshooting Problem No Input Voltage Problem TV does not Work Problem Low Battery Alarm on all the TimeSpecifications Description Specifications EN900Specifications EN1100 Warranty and Return Warranty by PowerBright Exclusions Return Procedure Return Material Authorization Policy