MODEL NUMBER

S 700

S 1000

 

S 1400

S 2000

Acceptable input voltage

 

0 - 165 VAC

 

Input voltage (on-line

 

80 - 150 VAC

 

operation)

 

 

 

 

 

 

 

Output voltage (AC Mode)

110/120V Settings: 104-130 VAC, 127V Setting: 104-134 VAC

Nominal input frequency

 

50 or 60 Hz, autosensing

 

Input protection

 

Resettable circuit breaker

 

Frequency limits (AC Mode)

 

50 or 60 Hz, +/-6Hz

 

Transfer time

 

2-6 mS typical

 

Maximum load

700VA

1000VA

 

1400VA

2000VA

 

500W

700W

 

1000W

1400W

On-battery output voltage

Default 120VAC / User

selectable at 110, 120, 127VAC

On-battery frequency

50/60 Hz, +/-.5 Hz, unless synchronized to utility

On-battery waveshape

 

True Sine Wave

 

Protection

Over current, short circuit protected and latching shutdown

Surge energy rating (one time,

 

500 J

 

10/1000 uS waveform)

 

 

 

 

 

 

 

Surge current capability

 

6500 Amps total

 

(one time, 8/20 uS waveform)

 

 

Surge response time

0 ns (instantaneous) normal mode; <5 ns common mode

Surge voltage let-through (as

 

<5%

 

 

a percentage of an applied

 

 

 

ANSI C62.41 Cat. A +/-6 kV)

 

 

 

 

 

Noise filter

Normal and common mode EMI/RFI suppression

Battery type: Sealed, non-

2-12V7Ah

2-12V12Ah

 

2-12V17Ah

2-12V17Ah

spillable, maintenance free,

 

lead-acid

 

 

 

 

 

Typical battery life

3-6 years, depending on discharge cycles and ambient temp

Typical recharge time

 

8 hours from total discharge

 

10 Base-T surge protection let-

 

 

 

 

 

through (as a percentage of

 

<5%

 

an applied +/-6 kV 1.2/50 us,

 

 

500 a 8/20 uS test)

 

 

 

 

 

Telephone line surge protec-

 

 

 

 

 

tion let-through (as a percent-

 

<1%

 

age of an applied +/-6 kV 1.2/

 

 

 

 

 

 

 

50 us, 500a 8/20 uS test)

 

 

 

 

 

Operating temperature

0 to 40 degrees C (+32 to 104 degrees F)

Storage temperature

-15 to +45 degrees C (+5 to +113 degrees F)

Operating elevation

 

0 to +3,000 m (0 to + 10,000 ft)

 

Storage elevation

 

0 to +15,000 m (0 to +50,000 ft)

 

Electromagnetic immunity

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

Audible noise at 1 m (3 ft.)

 

<45 dBA

 

Size - Net (Shipping)

8.9 x 6.5 x 17.8" / 226.1 x 165.1 x 452.1 mm

H x W x D

(12.8 x 10.8 x 21.7" / 325.1 x 274.3 x 551.2 mm)

Weight - Net (Shipping)

38.6 (42)lb

46.3 (50)lb

 

61.7 (65)lb

67.2 (71)lb

17.5 (19)Kg

21 (22.5)Kg

 

28 (29.5)Kg

30.5 (32)Kg

 

 

Safety and approvals

UL1778, UL497A,

UL497B, cUL (CSA 22.1)

EMC Verification

FCC Class B, CE certified

 

FCC Class A, CE certified

16

Image 17
Contents Page English Important Safety Instructions Materials Authorized Service Personnel onlyFront Panel SWF Front Panel IndicatorsRear Panel Installation PlacementConnecting Your Equipment InstallationChecking the Site Wiring Fault Connecting the UPS to AN AC SourceCharging the Battery Communications Port Connection OptionalSelf Test DIP Switch SettingsTurning the Unit ON/OFF UPS Fault Alarms On BatteryReplace Battery LOW Battery WarningSymptom Possible Cause What To Do Authorized Service Personnel only Replacing the BatteryBattery Replacement Procedure English If the UPS Requires Service Model Number EPO Customized Output Receptacle Panels Limited Product Warranty Limited Product Warranty Declaration of Conformity 224 PN 34000196 Rev