English
SYSTEM SPECIFICATIONS
Model Number | E750RM2U |
E1000RM2U
E1500RM2U
E1500RMT2U
E2000RM2U
E3000RM2U
E3000RMT2U
| Topology |
|
| |||
|
|
|
|
|
|
|
| Maximum Power Capacity | 750VA | 1000VA | 1500VA | 2000VA | 3000VA |
| 600W | 800W | 1200W | 1760W | 2560W | |
|
| |||||
|
|
|
|
|
|
|
|
|
| INPUT |
|
|
|
| Number of Phase |
| Single (1∅ 2W +G) |
| ||
|
|
|
|
|
|
|
| Nominal Voltage |
| 120VAC (208VAC) |
|
| |
|
|
|
|
|
| |
| Acceptable Input voltage |
| 0 - 165VAC (0 - 300VAC) |
| ||
|
|
|
|
|
| |
| Voltage Range |
| 80 - 164VAC (150 - 271VAC) |
| ||
|
|
|
|
|
| |
| Frequency Limits |
| 50 or 60 Hz, |
|
Low Voltage Transfer Point 80V (150V) resets to Utility Power at 85V (157V) or higher
High Voltage Transfer Point 164V (271V) resets to Utility Power at 159V (264V) or lower
Input ProtectionResettable Circuit Breaker
| OUTPUT |
| |
Voltage Range | 120VAC: 105 - 134VAC (208VAC: 189 - 236VAC) |
|
|
Voltage Regulation | 120VAC: |
|
|
Frequency Range | 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz |
|
|
Efficiency (Line Mode) | >93% (Full Load) |
|
| OUTPUT BATTERY OPERATION |
|
| |
|
|
|
| Waveform Type | Sine Wave |
|
|
|
| Nominal Voltage | Default: 120VAC (208VAC), User selectable: 127VAC (240VAC) |
|
|
|
| Voltage Regulation | Nominal |
|
|
|
| Frequency | 50/60Hz, |
|
|
|
| Voltage T.H.D. | <5% (Linear Load) |
|
|
|
| Dynamic Response | |
|
|
|
| Transfer Time | |
|
|
|
| Slew Rate | <1Hz / second |
|
|
|
| Overload Capacity | 110% for |
| 125% for | |
|
| 150% Shutdown Immediately |
|
|
|
| Protection |
23