CONNECTING THE BATTERY PACK
(QUALIFIED SERVICE PERSONNEL ONLY)
NOTE: If you are using these Battery Packs with the Endeavor series UPS, the UPS must be configured so that the UPS will report the correct estimated runtime in the SentryPlus software and to make the Battery capacity bar graph LEDs display properly. See the SentryPlus software User’s Manual to configure the UPS.
1.Make sure that the DC circuit breaker on the rear panel of the Battery Pack is in the Off position.
2.Turn the UPS off and disconnect the UPS's input power cord from the AC wall outlet.
3.Remove the External Battery Connector cover from the UPS's rear panel.
4.Verify, before connecting the Battery Pack's external battery cable into the UPS's external battery connector, that they mate red to red and black to black. NOTE: The red connector is the battery positive (+) and the black connector is the battery negative
5.See Connecting the Battery Pack to an AC Source.
NOTE: The EDBP72XL's External Battery Cable has a strain relief that must be attached (with the screw) to the rear panel of the UPS.
EDBP72XL's External Battery Cable with strain relief.