CONNECTING THE BATTERY PACK TO AN AC SOURCE

These Battery Packs can operate with 115VAC or 230VAC input voltage. Be- fore connecting the Battery Pack to an AC Source, verify that the Battery Pack's dipswitch is set for the proper input voltage.

1.Set the dipswitch on the rear panel of the Battery Pack to the appropriate input voltage.

2.Connect the input power cord for the Battery Pack into the AC Inlet on the Battery Pack.

3.Plug the other end of the input power cord for the Battery Pack into the AC wall outlet, use a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, or surge strips.

4.Turn the DC circuit breaker to the On position. See the UPS User's Manual for the normal startup of the UPS. NOTE: If connecting more than one Battery Pack see Daisy Chaining.

CHARGING THE BATTERY

The Battery Packs will charge the internal batteries whenever the Battery Pack is connected to an AC source and there an acceptable AC voltage present. It is recommended that the Battery Packs be charged for a minimum of 4 hours before use. The Battery Pack maybe used immediately, however, the “On- Battery” runtime of the UPS may be less than normally expected. NOTE: If the Battery Pack is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at least 24 hours every ninety days.

DAISY CHAINING

(QUALIFIED SERVICE PERSONNEL ONLY)

"Daisy Chaining" means hooking one Battery Pack to another Battery Pack to another Battery Pack, this chain could go on indefinitely. Follow the steps below to Daisy Chain the Battery Packs.

1.Be sure to read the installation placement procedure, all of the cautions and the safety precautions before Daisy Chaining the Battery Pack(s).

2.Make sure that all, the Battery Pack's DC circuit breakers and UPS's power switch, are in Off position. CAUTION: If the Battery Pack's DC circuit bre- aker is in the On position, the battery voltage will be present at the open end of the Battery Pack's external battery cable and external battery conn- ector. Unplug all the equipment that is plugged into the UPS's output rece- ptacles. Disconnect the power cords, that are on the Battery Packs and the UPS, from the AC wall outlet.

3.Remove the External Battery Connector cover from the UPS's rear panel and the additional Battery Packs.

4.Verify, before plugging the external battery cable into the UPS's external battery connector or the Battery Pack's external connector that they mate red to red and black to black.

5.Connect the external battery cable from the first Battery Pack to the exter- nal battery connector on the UPS.

6.Connect the external battery cable from the second Battery Pack to the ex- ternal battery connector on the first Battery Pack.

12

Image 13
Contents Endeavor Series Battery Packs English Important Safety Instructions English EDBP24XL EDBP48XL EDBP72XL UPS Please Save the Packing Materials Receiving InspectionRear Panel Indicator PanelInstallation Installation PlacementRackmount Configuration Wallmount Configuration Tower ConfigurationWallmount Configuration Qualified Service Personnel only Connecting the Battery PackCharging the Battery Connecting the Battery Pack to AN AC SourceDaisy Chaining English Dipswitch Settings Turning the Battery Pack ON/OFFIndicators System OverviewInto the AC wall outlet Formed by Qualified Service Personnel only Replacing the BatteryBattery Replacement Procedure English English If the UPS Requires Service System Specifications English Limited Product Warranty English