Minuteman UPS Endeavor user manual System Specifications

Page 22

English

SYSTEM SPECIFICATIONS

Model Number

EDBP24XL

EDBP48XL

 

EDBP72XL

 

 

 

 

 

Format

 

Rack/Tower Convertible

 

 

CHARGER INPUT

 

Number of Phases

Single (12W +G)

 

 

Nominal Voltage

115/230VAC (dipswitch selectable)

 

 

Voltage Range

115VAC: 90 - 130VAC (230VAC: 180 - 260VAC)

 

 

AC Current

2.6 Amps

 

 

Frequency Limits

50 or 60 Hz, +/-6Hz, autosensing

 

 

Input Protection

Resettable Circuit Breaker

CHARGER OUTPUT

DC Voltage

27.6VDC +/-5%

 

55.2VDC +/-5%

 

82.8VDC +/-5%

 

 

 

 

 

 

DC Current

 

 

2.4 Amps

 

 

 

 

 

 

 

Output Protection

 

Resettable Circuit Breaker

 

BATTERY SYSTEM

 

Battery Type

Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid

 

Typical Recharge Time

8-hours from total discharge

 

 

 

 

 

 

 

 

Typical Battery Life

3-5 years, depending on discharge cycles and ambient temperature

 

 

 

 

 

 

 

System Voltage

24VDC

48VDC

 

72VDC

 

 

 

 

 

 

 

System Current

 

40 Amps

 

 

 

 

 

 

 

 

Battery Qty/Rating

4 - 12V8.5Ah

8 - 12V8.5Ah

 

6 - 12V8.5Ah

 

 

 

 

 

 

 

 

PHYSICAL

 

 

 

 

 

 

 

 

Size - Net

13.1 x 17.3 x 3.5"

17.0 x 17.3 x 3.5"

 

L X W X H

335 x 440 x 89 mm

432 x 440 x 89 mm

 

 

 

 

 

 

 

Weight - Net

39.6 lbs

66.0 lbs

 

55.0 lbs

 

18.0 Kgs

30.0 Kgs

 

25.0 Kgs

 

 

 

 

 

 

 

 

 

Size - Shipping

23.6 x 20.0 x 9.0"

23.6 x 20.0 x 9.0"

 

L X W X H

600 x 508 x 230 mm

600 x 508 x 230 mm

 

 

 

 

 

 

 

Weight - Shipping

49.0 lbs

75.0 lbs

 

64.0 lbs

 

22.0 Kgs

34.0 Kgs

 

29.0 Kgs

 

 

 

 

 

 

 

 

 

 

 

REGULATORY COMPLIANCE

 

 

 

 

 

 

 

Safety and Approvals

UL1778, cUL (CSA 22.2 no. 107.1)

 

 

 

 

 

 

EMC Verification

FCC Class A, CE certified

 

21

Image 22
Contents Endeavor Series Battery Packs English Important Safety Instructions English EDBP24XL EDBP48XL EDBP72XL UPS Receiving Inspection Please Save the Packing MaterialsIndicator Panel Rear PanelInstallation Placement InstallationRackmount Configuration Tower Configuration Wallmount ConfigurationWallmount Configuration Connecting the Battery Pack Qualified Service Personnel onlyCharging the Battery Connecting the Battery Pack to AN AC SourceDaisy Chaining English Indicators Turning the Battery Pack ON/OFFDipswitch Settings System OverviewInto the AC wall outlet Replacing the Battery Formed by Qualified Service Personnel onlyBattery Replacement Procedure English English If the UPS Requires Service System Specifications English Limited Product Warranty English