Studer Innotec SI SERIES Studer Innotecsi, 1212, 1624, 2324, 3324, 3548, 1224, 2348, 1248

Page 10
STUDER INNOTECSI

STUDER INNOTECSI

Technical data

Model SI

612

812

 

1212

1624

2324

3324

3548

 

624

824

1224

 

2348

 

 

 

648

 

1248

 

 

 

 

Input voltage (Unom) [V]

12/24/48

12/24

12/24/48

24

24V/48

24

48

 

 

 

 

 

 

 

 

 

Nominal power [W]

600

800

1200

1600

2300

3300

3500

 

 

 

 

 

 

 

 

 

« Standby » current [mA]

25/21/10

25/21

25/21/12

21

25/17

25

30

Power « ON » no load [W]

2.6

2.8

4.8

5.8

9

13

17

 

 

 

 

 

 

 

 

 

Power « ON » no load [W]

--------

-------

< 0.5

< 0.5

< 0.6

< 0.7

< 0.8

TWINPOWER system

 

 

 

 

 

 

 

 

Maximum efficiency [%]

91

92

93 - 95

93 - 95

95

95

95

 

 

 

 

 

 

 

 

 

Length L x 124 (H) x 215 (W) [mm]

276

276

391

391

591

636

791

 

 

 

 

 

 

 

 

 

Weight [kg]

6.9

10.4

13.2

15.2

27

30

38

 

 

 

 

 

 

 

 

 

Input voltage

Dynamic correction of Umin.

Output voltage

Distortion

Dynamic behaviour

Frequency

Charge detection (standby)

Maximum power 15 min

Maximum power 3 min

Peak power 5s

Asymmetric load

Cos ϕ

Protections

IP protection index

Forced ventilation

Overheating protection

Required battery capacity

Acoustic level

EEC conformity

Min. - Max.: < Unom x 0.95 to Unom x 1.33 - 10% at Pnom

True sine 230 Vac ±3% < 2% (at Pnom)

From 0% to 100% load change. Normalization: 0.5 ms

50Hz ±0.01% (Crystal control) Adjustable: 0.3 20 W

1.3 – 1.6 x Pnom / 25°C

1.6 – 2 x Pnom / 25°C

3.5 x Pnom

Up to 2 x Pnom 0.1 – 1

Overload/Overheat/Short-circuit/Reverse polarity by internal fuse IP 20 complies with DIN 40050/IP 23 with top cover

From 45°C ± 3°C 75°C ± 3°C

> 5x Pnom/Unom (recommended value)

Without ventilation: < 10 dB

With ventilation:< 35 dB

EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC

Options

3-phased system (per unit) from SI 1200

SIxxxxPE

TwinPower system from SI 1200

SIxxxxTP

Top cover IP 23

C-IP23

 

SIxxxxA

Potential free alarm contact (60V/0.5A) for all models

Solar charge controller 16A/12-24V for SI 600 and SI 800

SIxxxS

Industrial casing in 19’’ rack – 3U x 400 mm from SI 1200

SIxxxxIND

Other specifications on request (Ex: 115V/60Hz).

These data are for information only and may change without notice.

SI in industrial casing 19’’ rack

User manual

SI V3.0 E

10

Image 10
Contents Users and Installers Handbook STUDER INNOTECSTUDER INNOTEC SI SERIESRed Fault - LED WIRING DIAGRAM FOR SI 600 - 800 S SOLAR CHARGE REGULATORAdjustment procedure DESCRIPTION AND WIRING DIAGRAMApplications and Performance After disconnecting the battery, the outputIntroduction Product presentationCheck the tension and polarity of the battery AssemblyRemote control ConnectionIndicators SafetyAdjustments Adjustment procedureOptions MaintenanceAlarm contact LegislationDescription and wiring diagram Wiring diagram for SI 600 - 800 S Solar charge regulator Working Option SI performance 3-phasedConnecting Commissioning1624 STUDER INNOTECSI1212 2324