Assembly
Location
The place where the inverter is to be mounted should meet the following requirements :
Out of reach of non authorised persons.
In a dry place with no condensation.
No inflammable material in the same room.
Not directly on top of the batteries.
Adequate ventilation. Keep min. 10 cm distance to other object (except mounting side)
Warning :
The casing of the inverter may reach high
temperatures (80 C°)
Fitting
The inverter has been designed to be used in a vertical position and against the wall. The inverter is fitted using the four external holes (∅ 5,5 mm).
The fitting screws are not supplied with the inverter.
Should the inverter be mounted on a flat surface, the maximum continuous power of the inverter may be slightly reduced.
Connection
Check the switch (4) is in “ OFF ” position.
First connect the 230V outlet (6) to the user device, so as to prevent any possible accidental contact.
SI
Check the tension and polarity of the
battery !
The tension of the battery should coincide with that mentioned in the technical characteristics of the inverter.
Battery connection :
This connection should done be very carefully observing the polarity in order not to damage the device.
Check that the connections are fixed correctly.
Use
After connecting the inverter, make sure the user devices are correctly plugged in and that there is no possible contact between the “ Line OUT ” (6) and a person.
The working device generates high tensions which could be fatal !
The inverter can be activated by moving the switch to the “ Auto ” position. The “ on ” indicator
SI xxxx model : If no user device is connected, the LED blinks after some seconds, which indicates that the “ standby ” mode has started. If a user device is plugged in, the green LED remains illuminated, indicating the uninterrupted presence of 230V in the outlet. If you wish to deactivate the standby mode, put the switch in
“Lock ” position. The inverter will be then working continuously.
SI xxxxTP model (Twinpower option) : The green LED remains illuminated indicating the uninterrupted presence of 230V in the outlet. The “ Lock ” function deactivates the economical mode.
Warning :
With the “lock” mode, the no load
consumption of the inverter is 15 to 20
times greater !
Remote control
The inverter can be controlled remotely with a switch
(5)connector on the under side of the device. The main switch (4) has priority over the working mode of the device. If the remote switch is close, the inverter is out of use.