NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, NETWORK MANAGEMENT CARD,
OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
High Bypass Point | +10% of | +5%, +10%, +15%, | Maximum voltage that the UPS | |
| output voltage | +20% | will pass to connected | |
| setting |
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
Low Bypass Point | Minimum voltage that the UPS | |||
| voltage setting |
| will pass to connected | |
|
|
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
Output Voltage | XLJ models: | XLJ models: | Allows the user to select the | |
| 200 VAC | 200 VAC | UPS output voltage while | |
| XLT models: | XLT models: | ||
| 208 VAC | 200, 208, 220, 230, |
| |
|
| 240 VAC |
| |
| XLTW models: | XLTW models: |
| |
| 220 VAC | 200, 208, 230, 240 VAC |
| |
| XLI models: | XLI models: |
| |
| 230 VAC | 200, 208, 220, 230, |
| |
|
| 240 VAC |
| |
|
| *Use the voltage setting |
| |
|
| applicable to your region. |
| |
|
|
|
| |
Output Frequency | Automatic | 50 ± 3 Hz | Sets the allowable UPS output | |
| (50 ± 3 Hz or | 50 ± 0.1 Hz | frequency. Whenever possible, | |
| 60 ± 3 Hz | the output frequency tracks the | ||
| 60 ± 3 Hz) | |||
| 60 ± 0.1 Hz | input frequency. | ||
|
| |||
|
|
|
| |
Number of Battery | 1 | Number of Connected | Defines the number of | |
Packs |
| Batteries (four battery | connected battery packs for | |
|
| modules per pack) | proper runtime prediction. | |
|
|
|
|
10