EPO (Emergency Power Off) Option

EPO (Emergency Power Off) Option

The output power can be disabled in an emergency by closing a switch connected to the EPO.

Adhere to national and local electrical codes when wiring.

The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by 12V internal supply. In closed condition, 2mA of current are drawn.

The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.

The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).

EPO switch

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the UPS to the EPO switch:

CL2: Class 2 cable for general use

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with local regulations.

11

Image 13
Contents Tower/Rack-Mount 6U English Uninterruptible Power Supply SURT 8000/10000 VA 200-240 VACSmart-UPS RT Page INSTALLATION SpecificationsRead the safety information sheet before installation IntroductionWiring must be performed by a qualified electrician HardwiringXLI MODEL XLT/XLJ/XLTW MODELSOUTPUT INPUTno pq rs Installing and Connecting the Batteries and Attaching the Front BezelOutput Circuit Breaker Input Circuit Breaker 8000/10000 VA XLI/XLJ/XLT/XLTW8000/10000 VA XLJ/XLT/XLTWExternal Battery Pack Use only interface kits supplied or approved by APCConnectors Serial PortOPERATION Troubleshootingaffect the voltage display On Battery OperationOPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE USER CONFIGURABLE ITEMSXLT models XLJ modelsXLTW models XLI modelsAdhere to national and local electrical codes when wiring EPO Emergency Power Off Option9 bits per second 9 data - bits 9 parity - none 9 stop bit Terminal Mode to Configure UPS Parameters9 flow control - none MAINTENANCE, SERVICE, WARRANTY, AND TRANSPORTING Replacing the Battery ModulesThe battery modules may remain in the UPS Transporting the UPSPROBLEM AND POSSIBLE TROUBLESHOOTINGSOLUTION CAUSEFAULT AND OVERLOAD LEDS ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE Replace Battery LED flashes andFAULT LED ILLUMINATES REPLACE BATTERY LED ILLUMINATESLimited Warranty ServiceThe batterys may remain in the UPS RADIO FREQUENCY WARNINGS APC Worldwide Customer Support