Smart Inventions 990-2689E manual Terminal Mode to Configure UPS Parameters, flow control - none

Page 14

Terminal Mode to Configure UPS Parameters

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial port on the back of the UPS.

1.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

2.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

9bits per second - 2400

9data - bits 8

9parity - none

9stop bit - 1

9flow control - none

Press ENTER

3.Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears on the screen prior to typing the next character.

Network Management Card defaults:

User Name: apc

Password: apc

Press 1 and ENTER to select Device Manager.

Select the model by entering the corresponding number, then press ENTER.

Press 3 and ENTER to select Configuration.

Press 1 and ENTER to select Battery.

Press 2 and ENTER to change the Battery Settings.

Type in the number of external battery packs (four battery modules per pack), then press ENTER. (Number of packs: 1= internal battery module,

2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)

Press 3 and ENTER to accept the changes.

Press ESC multiple times (5) to return to the main menu.

Press 4 and ENTER to log out.

12

Image 14
Contents Smart-UPS RT Uninterruptible Power Supply SURT 8000/10000 VA 200-240 VACTower/Rack-Mount 6U English Page Read the safety information sheet before installation SpecificationsINSTALLATION IntroductionHardwiring Wiring must be performed by a qualified electricianOUTPUT XLT/XLJ/XLTW MODELSXLI MODEL INPUTInstalling and Connecting the Batteries and Attaching the Front Bezel no pq rs8000/10000 VA Input Circuit Breaker 8000/10000 VA XLI/XLJ/XLT/XLTWOutput Circuit Breaker XLJ/XLT/XLTWConnectors Use only interface kits supplied or approved by APCExternal Battery Pack Serial PortTroubleshooting OPERATIONOn Battery Operation affect the voltage displayUSER CONFIGURABLE ITEMS OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODEXLTW models XLJ modelsXLT models XLI modelsEPO Emergency Power Off Option Adhere to national and local electrical codes when wiring9 flow control - none Terminal Mode to Configure UPS Parameters9 bits per second 9 data - bits 9 parity - none 9 stop bit The battery modules may remain in the UPS Replacing the Battery ModulesMAINTENANCE, SERVICE, WARRANTY, AND TRANSPORTING Transporting the UPSSOLUTION TROUBLESHOOTINGPROBLEM AND POSSIBLE CAUSEFAULT LED ILLUMINATES Replace Battery LED flashes andFAULT AND OVERLOAD LEDS ILLUMINATE UPS EMITS A SUSTAINED ALARM TONE REPLACE BATTERY LED ILLUMINATESThe batterys may remain in the UPS ServiceLimited Warranty APC Worldwide Customer Support RADIO FREQUENCY WARNINGS