MGE UPS Systems 40-75KVA UPS Connections, Main AC Input Connections, AC Output Connections

Page 21

Installation and User Manual

2.3.1UPS Connections

Electrical connections and cabinet interconnection will vary depending upon the configuration and options selected with your Galaxy 4000 UPS system. Refer to the installation drawings supplied with your equipment.

Connecting Power Cable Connections:

To access the connection terminal blocks, open the right door to the Galaxy 4000 UPS. Remove the safety panel located in the lower right hand section of the unit. See Figure 2-1.

a.The ground and neutral conductors must be connected to the ground and neutral busbars, respectively. The input and output neutral are connected at the neutral busbar.

b.Connect the three conductors of the main AC source to terminal block TB1.

c. If bypass source is present, connect the conductors of the bypass AC source to terminal block TB3. If bypass source is not present, verify jumpers in place between TB1 and TB3.

d.Connect the three conductors supplying the load to terminal block TB2.

e.Connect the battery conductors to the positive and negative busbars.

f.Secure all cables with cable ties.

g.Put all panels and covers back in place.

2.3.2Main AC Input Connections

The connections to be made are the three phases, neutral, and ground cables from the utility AC power source to the UPS. The main AC input cables are terminated at the main input terminal block (TB1). See Figure 2-1.

IMPORTANT For single input (optional configuration), jumper cables are provided from terminal blocks TB1 to TB3.

2.3.3Bypass AC Input Connections (optional)

The bypass AC input cables are terminated at the bypass input terminal block (TB3). This option provides a separate AC input source for bypass operation. See Figure 2-1.

2.3.4AC Output Connections

The connections to be made are the three phases, neutral, and ground cables from the load to the UPS. The output cables are terminated at the output terminal block (TB2). See Figure 2-1.

86-173010-00 A00

Installation

2 — 3

Image 21
Contents Galaxy Page Revision History GalaxyGalaxy Important Safety InstructionsSafety of Persons Product SafetySpecial Precautions Galaxy Contents Maintenance Display PanelOperation Glossary Reorder Form Warranty, Registration & Customer SupportTables FiguresElectrical Section DescriptionsGalaxy Introduction ScopeGeneral Description Major Components Single Line DiagramGalaxy 4000 Standard Cabinets Cabinet PlacementPreparation for Operation Heat Rejection and Air FlowCabinet Clearances Heat Rejection Data @ 208/208VACConduit Plate Locations for Bottom Entry 40KVA 50KVA 65KVA 75KVAConduit Plate Locations for Top Entry Configuration for Bottom EntryPreparation for Storage Installation Steps Setup and InstallationFinal steps by MGE Field Service Engineer Environmental and Electrical SpecificationsElectrical Specifications Electrical Connections40KVA 50KVA 65KVA UPS Connections Main AC Input ConnectionsAC Output Connections Remote Emergency Power Off Connections Battery ConnectionsRelay Communication Card Contacts InputsOutputs Relay Communication Card Relay Communication Card ConnectionsConsumption 10 mA Cable 0.34 mm, 5 ±0.5 mm 5VDCThis page left blank intentionally Display Panel Operator Interface Keys and IndicatorsGreen LED Orange LED Red LED LED Indicator FunctionsFlashing OFFDisplay Menu Structure Battery Measurements Screen Main Menu ScreenMeasurements Power Measurements Screen Magnifying glassCurrent Measurements Screen Voltage Measurements Screen Frequency Measurements ScreenRatios Screen Status Screen Mimic DiagramsSettings Screen Startup Procedure Screen Commands ScreenThis page left blank intentionally Display Panel Pre-Startup Safety Check List OperationPreparing for Startup Q3BP Q4SQ5N Normal Startup Procedure Shutdown Procedure Post Startup Safety Check ListShutdown Using EPO Recovery from EPOMaintenance Important Safety Instructions for Servicing BatteriesServicing Batteries This page left blank intentionally Applicable within the United States, Canada and Mexico Warranty Extension Warranty+ Galaxy Warranty and Product RegistrationUser Information Product InformationTechnical Support and Product Services MGE Customer Care Center Three Phase ProductsScheduling Field Service Engineer Support Return Policy for Repair of Three Phase Products RGAAdditional Serial Numbers ABC GlossaryIEC NEC This page left blank intentionally Galaxy 40 75KVA Reorder FormPage Page Page Page Contact MGE

40-75KVA specifications

MGE UPS Systems 40-75KVA represents a significant advancement in uninterruptible power supply technology, specifically designed to cater to the critical needs of medium to large-scale operations. These systems are integral for protecting sensitive electronic equipment and ensuring the continuity of operations during power disturbances.

One of the standout features of the MGE UPS Systems in this range is their high efficiency. With efficiency ratings often exceeding 94%, these units minimize energy loss and reduce operational costs, making them not only environmentally friendly but also financially viable. The robust design caters to a variety of applications, including data centers, telecommunications facilities, and industrial environments.

A cornerstone of the MGE UPS design is its modular architecture, allowing for scalability and flexibility. This modularity ensures that as power requirements increase or decrease, the system can be easily adjusted to meet those needs without replacing the entire unit. This adaptability is critical for businesses that experience fluctuating demand or growth.

Advanced technology is employed in the battery management system as well. MGE UPS Systems utilize intelligent battery management, which enhances battery performance and lifespan. The system continuously monitors battery health and ensures optimal charging, thus reducing the risk of failure and extending operational readiness.

The MGE UPS Systems 40-75KVA also boast user-friendly interfaces with graphical LCD displays, facilitating easy monitoring and management of the power supply status. Users can access relevant data such as load levels, battery status, and system health, simplifying troubleshooting and maintenance tasks.

Additionally, these UPS systems incorporate multiple forms of communication interfaces, including USB, RS232, and network management options, ensuring seamless integration with other system monitoring tools. This connectivity enhances operational oversight and aids in proactive management of power resources.

Furthermore, the high availability features, such as redundant components and hot-swappable modules, ensure that maintenance can be performed without interrupting operations, significantly reducing downtime.

In conclusion, MGE UPS Systems 40-75KVA encapsulate cutting-edge technology with unique features that prioritize efficiency, flexibility, and reliability. With their robust design tailored for demanding environments, they are an optimal choice for organizations seeking to safeguard their critical operations against power interruptions. The combination of advanced battery management, user-friendly interfaces, and scalable architecture makes these systems a smart investment for the future.