MGE UPS Systems 40-75KVA Post Startup Safety Check List, Shutdown Procedure, Shutdown Using EPO

Page 40

Galaxy 4000

4.3Post Startup Safety Check List

After initial startup of the system, normal operation should be tested. At the minimum, the following tests should be performed as applicable to your installation.

Emergency Power Off (EPO) test.

Remote Emergency Power Off (REPO) test (if applicable).

Inverter start and stop.

Battery transfer test.

Maintenance bypass procedure.

CAUTION As soon as AC input power is supplied to the Galaxy 4000 (customer supplied upstream circuit breaker is in the "ON" position), the load is initially supplied via the "Static Switch". Verify that no error indications are present on the operator interface display panel.

4.4Shutdown Procedure

Proceed as follows:

1.Press the gray, Inverter OFF button.

2.Confirm by pressing the function key.

The load is no longer protected by the UPS. It is supplied via the bypass.

3.Set the battery circuit breakers CB1 (in battery cabinet) to the OFF position.

4.Close Q3BP, open input switch Q1, bypass switch Q4S, and output breaker Q5N.

5.To completely remove power from the UPS, open Q3BP and open the upstream circuit breakers supplying AC power to switches Q1 and Q4S. Attention: There is no power to the load.

4.5Shutdown Using EPO

During an emergency situation the UPS and all downstream devices can be instantly shutdown by pressing the red emergency power off (EPO) pushbutton on the front door of the UPS cabinet, or pressing the remote emergency power off (REPO) pushbutton (if applicable) located within the room.

IMPORTANT Pressing the EPO button disconnects the attached load. The emergency power off (EPO) is to be used during emergency situations only, where a hazard to personnel or equipment exists.

4.6Recovery from EPO

To recover from an emergency power off press the EPO pushbutton again. Follow the normal startup procedure in Section 4.2.

NOTE

The EPO pushbutton is a latching device. The EPO condition will remain until the

 

EPO button is depressed a second time.

 

 

4 — 4

Operation

86-173010-00 A00

Image 40
Contents Galaxy Page Galaxy Revision HistoryImportant Safety Instructions GalaxyProduct Safety Safety of PersonsSpecial Precautions Galaxy Contents Display Panel MaintenanceOperation Warranty, Registration & Customer Support Glossary Reorder FormFigures TablesSection Descriptions ElectricalGalaxy Scope IntroductionGeneral Description Single Line Diagram Major ComponentsCabinet Placement Galaxy 4000 Standard CabinetsPreparation for Operation Heat Rejection and Air FlowHeat Rejection Data @ 208/208VAC Cabinet ClearancesConduit Plate Locations for Bottom Entry 40KVA 50KVA 65KVA 75KVAConfiguration for Bottom Entry Conduit Plate Locations for Top EntryPreparation for Storage Setup and Installation Installation StepsFinal steps by MGE Field Service Engineer Environmental and Electrical SpecificationsElectrical Connections Electrical Specifications40KVA 50KVA 65KVA Main AC Input Connections UPS ConnectionsAC Output Connections Battery Connections Remote Emergency Power Off ConnectionsInputs Relay Communication Card ContactsOutputs Relay Communication Card Connections Relay Communication Card5VDC Consumption 10 mA Cable 0.34 mm, 5 ±0.5 mmThis page left blank intentionally Operator Interface Keys and Indicators Display PanelLED Indicator Functions Green LED Orange LED Red LEDFlashing OFFDisplay Menu Structure Main Menu Screen Battery Measurements ScreenMeasurements Magnifying glass Power Measurements ScreenCurrent Measurements Screen Frequency Measurements Screen Voltage Measurements ScreenRatios Screen Mimic Diagrams Status ScreenSettings Screen Commands Screen Startup Procedure ScreenThis page left blank intentionally Display Panel Operation Pre-Startup Safety Check ListPreparing for Startup Q4S Q3BPQ5N Normal Startup Procedure Post Startup Safety Check List Shutdown ProcedureShutdown Using EPO Recovery from EPOImportant Safety Instructions for Servicing Batteries MaintenanceServicing Batteries This page left blank intentionally Applicable within the United States, Canada and Mexico Galaxy Warranty and Product Registration Warranty Extension Warranty+User Information Product InformationMGE Customer Care Center Three Phase Products Technical Support and Product ServicesScheduling Field Service Engineer Support Return Policy for Repair of Three Phase Products RGAAdditional Serial Numbers Glossary ABCIEC NEC This page left blank intentionally Reorder Form Galaxy 40 75KVAPage Page Page Page Contact MGE

40-75KVA specifications

MGE UPS Systems 40-75KVA represents a significant advancement in uninterruptible power supply technology, specifically designed to cater to the critical needs of medium to large-scale operations. These systems are integral for protecting sensitive electronic equipment and ensuring the continuity of operations during power disturbances.

One of the standout features of the MGE UPS Systems in this range is their high efficiency. With efficiency ratings often exceeding 94%, these units minimize energy loss and reduce operational costs, making them not only environmentally friendly but also financially viable. The robust design caters to a variety of applications, including data centers, telecommunications facilities, and industrial environments.

A cornerstone of the MGE UPS design is its modular architecture, allowing for scalability and flexibility. This modularity ensures that as power requirements increase or decrease, the system can be easily adjusted to meet those needs without replacing the entire unit. This adaptability is critical for businesses that experience fluctuating demand or growth.

Advanced technology is employed in the battery management system as well. MGE UPS Systems utilize intelligent battery management, which enhances battery performance and lifespan. The system continuously monitors battery health and ensures optimal charging, thus reducing the risk of failure and extending operational readiness.

The MGE UPS Systems 40-75KVA also boast user-friendly interfaces with graphical LCD displays, facilitating easy monitoring and management of the power supply status. Users can access relevant data such as load levels, battery status, and system health, simplifying troubleshooting and maintenance tasks.

Additionally, these UPS systems incorporate multiple forms of communication interfaces, including USB, RS232, and network management options, ensuring seamless integration with other system monitoring tools. This connectivity enhances operational oversight and aids in proactive management of power resources.

Furthermore, the high availability features, such as redundant components and hot-swappable modules, ensure that maintenance can be performed without interrupting operations, significantly reducing downtime.

In conclusion, MGE UPS Systems 40-75KVA encapsulate cutting-edge technology with unique features that prioritize efficiency, flexibility, and reliability. With their robust design tailored for demanding environments, they are an optimal choice for organizations seeking to safeguard their critical operations against power interruptions. The combination of advanced battery management, user-friendly interfaces, and scalable architecture makes these systems a smart investment for the future.