MGE UPS Systems EX 5RT, EX 11RT, EX 7RT user manual Output

Page 41

Installation and User Manual

2.8.4System Connections with Separate Normal and Bypass AC Sources

CAUTION:

This installation requires 2 AC input source with Line, Neutral plus Ground,

 

(200-240VAC). Neutral points are connected together inside the UPS.

 

 

Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.

O

1

OFF

 

Proceed as follows:

1.Remove the cover plate under the I/O Box. Loosen the terminal blocks L1 and L3, and remove the jumper.

OFF

O

3Output

 

 

 

66074

 

Settings

 

 

 

Card

 

 

 

UPS

data

ETHERNET

 

100 10

IP=

MAC=00E0D8FF855E

Reset

RS232Download

L3 L1

2

Bypass

Normal

4

OFF

O

To Step-Down

Transformer (if applicable)

CAUTION: Always connect the earth ground wire first.

2.See section 2.8.1 and I/O Box terminal diagram for installation of Normal AC Input, Bypass AC source, and Output cable with different wire style.

3.Reinstall the cover plate under the I/O Box with four screws.

4.Secure the I/O Box to the power module using three screws.

See section 2.8.3 for connecting EX RT Transformer, if applicable.

86-86000-00 A01

Installation

2 — 17

Image 41
Contents EX 5RT / EX 7RT/ EX 11RT System Certification Standards EX 5/7/11 RT SystemHow to use this manual and Symbol Usage Safety of PersonsAdditional Modules Serial Numbers Revision History EX 5/7/11 RT SystemMGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714 800This page left blank intentionally Contents Operation EX 5/7/11 RT System Setup and InstallationMGE Warranty & Propriety Rights MaintenanceWarranty and Product Registration Technical Support and Field ServiceFigures Figures TablesThis page left blank intentionally Scope IntroductionEX RT Model Descriptions and Contents Part Number Description Standard Configurations System Electrical CharacteristicsTower Configuration Part Number 86055 86075 86115Model Dimensions Weights Rack ConfigurationRear panel of the Power Module Rear Panels Power Module EX 5/7/11 RTDisplay and Control Panel EX RT Transformer ModuleBattery/ Transformer/CLA Module Rail Kit Optional AccessoriesPower Module Rail Kit Battery Extension Cable Kit Battery Module with Remote Emergency Power Off Repo FunctionInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents CLA Module Contents All Modules are shipped in separate boxes Setup and InstallationUnpacking and Parts Check Contents of EX 5/7/11 RT System 3335 Installation Installation in Tower ConfigurationTransformer on top for optimum stability Accessing Battery Pack Prepare Battery Module for Rack MountingRack mounting of the power module onto the rails Power or Battery Module Rack MountingInput/Output Box Bracket System Installation Rear Support Brackets InstallationInstalling I/O Box bracket system Rear support brackets must be removed prior toCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Network Management Card Connecting the Dry Relay Contact Communication PortContact normally open Contact normally closedDual U-Talk/Basic Card Alarm Relay CardModBus Card Dual COM Ports CardRemote Emergency Power Off Repo Communication Port Knockout die stamp circles Flexible Cordage and Conduit Installations L6 L5 L2 L1 L1 L4 L3 Jumper Terminals System Connections with Common Normal and Bypass AC SourcesLb Ld N Lc La Connecting EX RT TransformerOutput 10100 Data 17 Rear view of battery module cable connections Connection of Battery Module, EXBConnection of CLA Module AC InputInitial Startup OperationUPS Personalization Accessing personalization with front panel buttonsDisplay Factory setting Options Comments Display Factory setting OptionsFinal startup sequence Accessing personalization through external softwareRemaining Time Operating Modes Normal double conversion ModeECO Modes ECO mode displayTransfer to Battery Power Operation on battery powerFirst Case Second CaseShutdown Return of Normal AC sourceSymptoms IT network mode Industrial mode MaintenanceSymptom Indication Correction TroubleshootingTroubleshooting requiring MGE after-sales support XXX Fault 1CXXXXXXX Hot Swapping the Power ModuleReconnect the power module Re-connecting the power moduleRe-connecting the Battery Module Hot Swapping the Battery ModuleDisconnecting the Battery Module System Overload Characteristics Electrical Specifications System Input/Output Power RatingsSystem Backup Characteristics AppendixEnvironmental Characteristics Accessories Electrical Characteristics EX RT TransformerSystem Short Circuit Protection EX RT CLA moduleProprietary Rights Statement MGE Warranty & Proprietary Rights for Single Phase ProductsMGE Warranty Product information Warranty Extension Warranty+ not available on productsUser Information MGE Customer Care Center EX 5/7/11 RT System Term used Definition / Meaning GlossaryIEC NEC This page left blank intentionally EX 5/7/11 RT System Reorder Form Scenic Avenue Costa Mesa, CAPage Page Contact MGE