Remove power at the electricity board meter (circuit breaker panel) of the home.

Figure 7 shows a diagram of a typical home wiring scenario. Figure 8 shows a typical home wiring scenario after installation of the Inverter Assembly wiring.

Note: The Power Inverter can serve inductive loads (flourescent lamps, ceiling and table fans), resistive loads (incandescent lamps), and SMPS loads (television). The typical backup time with the primary battery pack at full load is approximately two (2) hours.

Caution: Connecting the Power Inverter to a branch circuit that exceeds 16 amps may result in equipment damage.

Note: Home wiring to power the desired loads should be routed and connected to a single branch circuit providing a maximum of 16 amps to the circuit, Wiring must be in accordance with local electric codes and standards. Connected loads must not exceed 500 watts when the Inverter is On Battery.

Double-Pole

Switch

Electricity

L

L

 

N

N

 

Board

Load

E

E

Meter

 

Existing Wiring

Figure 7. Typical Home Wiring Before Inverter Installation

Page 7

Image 10
Contents Power Inverter Contents Contents Overview Battery Handle Fluid Level Installation Main Housing Placement Do Not Remove These Two Screws Battery Installation Inverter Assembly Placement Electricity Load Board Kit Alignment Pins Holes 4 places Power Inverter Indicators Battery Power Inverter Troubleshooting Push to Reset Input 5A, 50Hz Output Specifications 15/Page 16 blank