| On Mains | On Battery | Fault |
| INV | 25% | 50% | 75% | 100% | Overload |
|
|
Mode |
| Disable | Buzzer | Description | ||||||||
(green) | (yellow) | (red) |
| (green) | (green) | (green) | (green) | (red) | ||||
|
| (red) |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
FAULT- | On | Flashing | Flashing | Off | Off | Off | Off | Off | Off | Chirps every 2.5 | The unit is in FAULT mode, | |
|
|
|
|
|
|
|
|
|
|
| seconds; sound is | contact APC Technical |
|
|
|
|
|
|
|
|
|
|
| mutable through the | Support. |
|
|
|
|
|
|
|
|
|
|
| front panel TEST/ |
|
|
|
|
|
|
|
|
|
|
|
| MUTE push button. |
|
|
|
|
|
|
|
|
|
|
|
|
| |
BATTERY | On | Off | Flashing | Off | Off | Off | Off | Off | Off | Chirp every 2 seconds | The unit is | |
DISCONNECTED |
|
|
|
|
|
|
|
|
|
|
| battery is disconnected. |
|
|
|
|
|
|
|
|
|
|
|
| |
OVER TEMP ON- | Off | Off | 4 flashes | Off | Off | Off | Off | Off | Off | Continuously On | The unit is in FAULT mode | |
BATTERY |
|
| every | 2 |
|
|
|
|
|
|
| due to over- temperature |
|
|
| second |
|
|
|
|
|
|
| condition. | |
|
|
|
|
|
|
|
|
|
|
|
| |
OVER TEMP ON- | On | Off | 4 flashes | Off | Off | Off | Off | Off | Off | Off | The unit is in | |
LINE |
|
| every | 2 |
|
|
|
|
|
|
| but the charger is switched off |
|
|
| second |
|
|
|
|
|
|
| due to over- temperature. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
ON LINE | On | Off | Off |
| On | Off | Off | Off | Off | Off | Off | The unit is in |
|
|
|
|
|
|
|
|
|
|
|
| the inverter is disabled and |
|
|
|
|
|
|
|
|
|
|
|
| the unit will not go ON |
|
|
|
|
|
|
|
|
|
|
|
| BATTERY during a power |
|
|
|
|
|
|
|
|
|
|
|
| failure. |
|
|
|
|
|
|
|
|
|
|
|
|
|
ON LINE SELF TEST | Flashing | Off | Off |
| On | Off | Off | Off | Off | Off | Off | The unit is in |
|
|
|
|
|
|
|
|
|
|
|
| Test mode, but the inverter is |
|
|
|
|
|
|
|
|
|
|
|
| disabled and the unit will not |
|
|
|
|
|
|
|
|
|
|
|
| go |
|
|
|
|
|
|
|
|
|
|
|
| power failure. |
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY SELF | Flashing | On | Off |
| On | On | Off | Off | Off | Off | Off | The unit is |
TEST |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| disabled and the unit will not |
|
|
|
|
|
|
|
|
|
|
|
| go |
|
|
|
|
|
|
|
|
|
|
|
| power failure. |
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY Low | Off | On | Off |
| Off | On | Off | Off | Off | Off | Constant Beeping, | Load is less than 25%. |
Battery Warning |
|
|
|
|
|
|
|
|
|
| Can be muted through |
|
|
|
|
|
|
|
|
|
|
|
| fron panel TEST/ |
|
|
|
|
|
|
|
|
|
|
|
| MUTE push button. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY Low | Off | On | Off |
| Off | On | On | Off | Off | Off | Constant Beeping, | Load is between 25% and |
Battery Warning |
|
|
|
|
|
|
|
|
|
| Can be muted through | 50%. |
|
|
|
|
|
|
|
|
|
|
| front panel TEST/ |
|
|
|
|
|
|
|
|
|
|
|
| MUTE push button. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY Low | Off | On | Off |
| Off | On | On | On | Off | Off | Constant Beeping, | Load is between 50% and |
Battery Warning |
|
|
|
|
|
|
|
|
|
| Can be muted through | 75%. |
|
|
|
|
|
|
|
|
|
|
| front panel TEST/ |
|
|
|
|
|
|
|
|
|
|
|
| MUTE push button. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY Low | Off | On | Off |
| Off | On | On | On | On | Off | Constant Beeping, | Load is between 75% and |
Battery Warning |
|
|
|
|
|
|
|
|
|
| Can be muted through | Overload limit. |
|
|
|
|
|
|
|
|
|
|
| front panel TEST/ |
|
|
|
|
|
|
|
|
|
|
|
| MUTE push button. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON BATTERY Low | Off | On | Off |
| Off | On | On | On | On | On | Constant Beeping, | Load is more than overlaod |
Battery Warning |
|
|
|
|
|
|
|
|
|
| Can be muted through | limit. |
|
|
|
|
|
|
|
|
|
|
| front panel push |
|
|
|
|
|
|
|
|
|
|
|
| TEST/MUTE button. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: In the case of a sustained overload, the Inverter will be turned off automatically after one minute, and will wait in the fault state for a minute. After that, it will restart again. If the overload still persists, the Inverter will be turned off again after one minute, and will wait in fault state for one minute and restart again. In the same way, it will try for three restarts. If the overload still persists, it will stay in fault state permanently until the unit is restarted with push button. If the time interval between two consecutive overloads is more than 5 mins, then the latest overload is considered as a fresh overload and three restart cycle will begin again.
Page 11