American Power Conversion AP7608, AP7602, AP7601 operation manual Wiring Options

Page 18

Wiring Options

6.Attach wires to the terminal block as labeled on the board. Tighten the terminal block screws to secure the wires.

Metered Rack-Mount PDU Terminal Block

L3

L2

L1

L3 L2 L1

7.Attach a ground wire to the standoff on the metal chassis and tighten the screw to secure the ground to the chassis.

8.Place the hardwiring access cover (part number 870-70804) on the PDU, and secure it with one screw in the hole on the top of the cover.

9.Apply power to the PDU, observing the status LED on the display interface. If the unit is connected properly, the LED will illuminate.

Additional power cord You can also use the power cord AP9870, available for purchase from

available from APC APC, with the Rack PDUs described in this manual. This power cord has the following cord ends (IEC 320 C13 to IEC 320 C14):

14

Three-Phase Rack PDU — Installation and Operation Manual

Image 18
Contents Three-Phase Rack Power Distribution Unit Page Contents Page Product Description and Inventory DescriptionInventory AP7601AP7602AP7608 How to Install the Rack PDUs Installation guidelinesMounting options Toolless mounting Into the bottom holes in the enclosureLocks into position Bracket-mounting Rack PDU to be mounted flush with the enclosure a raisedHead screws provided in the bracket kit for each bracket Recessed Orientation Raised Orientation PDU through a serial ConfigurationHow to configure PortStatus Information Device Data, main menu option 3, has the following settings Device Data optionSystem Management Factory Data optionLogout option OptionOperation Display interfaceAlarm conditions Using a serial port connectionRack PDU shows warning and alarm conditions as follows Wiring Options Hardwiring procedure optionalWiring Options Specifications ElectricalHow to Download Firmware Updates XmodemWarranty limitations Warranty and ServiceLimited warranty Obtaining servicePage Radio Frequency Interference APC Worldwide Customer Support