American Power Conversion 7500/10000 VA user manual User Configurable Items

Page 11

3:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, WEB/SNMP CARD, OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-Test

Every 14 days

Every 7 days

Set the interval at which the

 

(336 hours)

(168 hours),

UPS will execute a self-test.

 

 

Every 14 days

 

 

 

(336 hours),

 

 

 

On Startup Only,

 

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

 

 

define the UPS

server name or location) for

 

 

 

network management purposes.

 

 

 

 

Date of Last Battery

Manufacture Date

mm/dd/yy

Reset this date when you replace

Replacement

 

 

the battery modules.

 

 

 

 

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Specify the percentage to which

Before Return from

 

90 percent

batteries will be charged

Shutdown

 

 

following a low-battery

 

 

 

shutdown before powering

 

 

 

connected equipment.

 

 

 

 

Alarm Delay After

5 second delay

5 second delay,

Mute ongoing alarms or disable

Line Failure

 

30 second delay,

all alarms permanently.

 

 

At Low Battery,

 

 

 

Never

 

 

 

 

 

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

 

 

720, 960 seconds

when the UPS receives a

 

 

 

shutdown command and the

 

 

 

actual shutdown.

 

 

 

 

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes.

become continuous when two

 

 

minutes of runtime remains.

 

software provides

 

 

automatic,

 

Change the warning interval to a

 

unattended

 

higher setting if the operating

 

shutdown when

 

system requires a longer interval

 

approximately two

 

for shutdown.

 

minutes of battery

 

 

 

runtime remains.

 

 

 

 

 

 

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

Specify the time the UPS will

Delay

 

720, 960 seconds

wait after the return of utility

 

 

 

power before turn-on (to avoid

 

 

 

branch circuit overloads).

 

 

 

 

9

Image 11
Contents APC Smart-UPSRT Page Removing the Batteries PlacementIntroduction UnpackingXLT, XLJ, and Xltw Models HardwiringXLT/XLJ/XLTW Models Page L6-20 L6-30 250V 20A 250V 30A Serial Port Operation Affect the voltage display On Battery OperationUser Configurable Items Models Adhere to national and local electrical codes when wiring EPO Emergency Power Off OptionTerminal Mode to Configure UPS Parameters Transporting the UPS Replacing the Battery ModulesStorage Troubleshooting Replace Battery LED flashes Contacting APC Service200, 208, 220, 230, 240 V Models Regulatory Agency Approvals and Radio Frequency WarningsDeclaration of Conformity Limited Warranty